max. L, N, PE
min. L, N, PE
REMOTE SIGNALLING
6
DÁLKOVÁ SIGNALIZACE
max. S
min. S
U
/I
MAX
MAX
U
/I
MAX
MAX
GRAPH
7
30
GRAF
25
20
15
10
5
0
20
Nominal current depending on ambient temperature
Závislost jmenovitého proudu In na teplotě okolí
INSTALLATION
8
INSTALACE
GB
- the line lenght between 2
be at least 5 m
- the length of the connecting lines between the arrester
(OUT) and the equipment to be protected must be as
short as possible. When connected in parallel, a lenght
of 0,5 m for the branch lines should not be exceeded.
- when installing, country-specific regulations and rules
have to be observed
Only materials which have low adverse environmental impact and which do not contain dangerous
9
substances as specified in ROHS directive have been used in the product.
Ve výrobku jsou použity materiály s nízkým negativním dopadem na životní prostředí, které neobsahují zakázané
nebezpečné látky dle ROHS.
AC
DC
30
40
nd
rd
a 3
protection stage must
8 mm
2
4 mm
2
0,2 mm
8 mm
2
4 mm
2
0,2 mm
250 V/ 3 A
125 V/ 0,2 A, 30 V/ 1 A
50
60
CZ
-délka vedení mezi 2. a 3. (tímto) stupněm ochrany musí
být minimálně 5 m
-délka vedení mezi výstupem svodiče (OUT) a
chráněným zařízením musí být co nejkratší. V případě
paralelního zapojení svodiče nesmí být překročena
délka 0,5 m pro odbočku.
-při instalaci musí být dodržovány národní předpisy a
směrnice
- 4 -
8 mm
2
2,5 mm
2
0,2 mm
8 mm
2
2,5 mm
2
0,2 mm
70
80
90
T °C
[
]
990383b Z00