V7 UPS2URM3000DC-NC-1E Manual De Instrucciones página 12

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

07: Bypass voltage range setting
Interface
08: Bypass frequency range setting
Interface
09: Programmable outlets enable/disable
Interface
10: Programmable outlets setting
Parameter 2: Enable or disable Bypass function.
ENA: Bypass enable
DIS: Bypass disable (Default)
Setting
Parameter 2: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from
230Vac to 264Vac. (Default: 264Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
Setting
Parameter 2: Set the acceptable high frequency point and
acceptable low frequency point for Bypass mode by pressing
the Down key or Up key.
HLS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: Set the frequency high loss point from 51Hz to
55Hz. (Default: 53Hz)
For 60Hz output frequency models:
61-65Hz: Set the frequency high loss point from 61Hz to
65Hz. (Default: 63Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: Set the frequency low loss point from 45Hz to
49Hz. (Default: 47Hz)
For 60Hz output frequency models:
55-59Hz: Set the frequency low loss point from 55Hz to
59Hz. (Default: 57Hz)
Setting
Parameter 2: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
11

Publicidad

Tabla de contenido
loading

Tabla de contenido