Install Software; Battery Replacement - V7 UPS2URM3000DC-NC-1E Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Powering on the UPS
NOTE: The battery will charge fully during the first five hours of normal operation. Full battery
run capability is not possible during the initial charge period.
Press the ON/Mute button on the front panel for two seconds to turn on the power to the UPS.

7. Install software

For optimal computer system protection, install UPS monitoring software to fully configure UPS
shutdown. Please follow steps below to download and install monitoring software.
1. Go to the website
2. Select ViewPower software for your operating system to download the software.
3. Follow the on-screen instructions to install the software.

1.5 Battery Replacement

Note: This UPS is equipped with internal batteries and only a trained technician should replace
the batteries.
Replace the batteries if icons
every 2 seconds.
Do not disconnect battery connectors under load. To remove input power to change the batteries,
press the OFF button on the front panel for two seconds to power off the UPS and switch off utility
power where the UPS is connected.
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
A small arc may occur when connecting the internal batteries. This is not harmful to the UPS or
personnel. Connect the cables quickly and firmly.
Step 1
Remove front panel.
https://www.v7world.com/ups-downloads
and
Step 2
Disconnect battery wires.
are flashing in the LCD display and alarm is sounding
5
Step 3
Pull out the battery box by