1.5.3 CA 443
Book_81307110_CA44x.indb 107
Book_81307110_CA44x.indb 107
Produktet har til formål at måle strømforbrug, faseafvigelse og spændingsindgang for en pumpe
eller en hel station.
If pump is operated from a frequency converter, special precautions are required.
The high electric noise level can distort electrical readings, especially phase timing readings are
sensitive to switch transients from frequency converter.
Turn off all phase related alarms and dry run detection in PC 441 and ensure PC 441 firmware ver-
sion is V.1.42 or later
Normal current transformers operate from 45-60 Hz and must be placed on mains line input to
frequency converter.
Use only mains phase (voltage) missing alarm for pump protection (blocking).
To avoid conducted electrical noise in cabinet, follow best practices and manufacturer EMC compli-
ance recommendation when installing frequency converters. Use shielded cables. Ensure mains
and motor cables are separated from signal cables in cabinet.
General precautions:
If CA 443 for P1 also is used for mains monitoring, L1, L2 and L3 voltage inputs must be connected
before pump circuit breaker.
Tabel 9.
Kapacitet for CA 443
Indgang
Spænding
30 - 300 V ac ± 5,0 V ac
0 - 5 A ± 0,1 A faseskift 0 - 90
Strøm
grd. ± 1,5 grd.
Tabel 10. Bundtilslutninger
Dir.
Signal
#
Sensor 1
6
Sensor 2
7
Sensor 3
8
GND
9
a Sensor 4
10
b GND
11
a Sensor 5
12
b GND
13
a Sensor 6
14
b GND
15
Tabel 11. CA 443 LED indicators from PC 441 firmware 1.42
LED
Indication
Mains monitor (0 or 1)
1
Phase 1
Voltage missing
2
Phase 2
Voltage missing
3
Phase 3
Voltage missing
4
Warning
Alarm wrong phase order
Alarm phase missing
Pending high voltage
Pending low voltage
Pending unbalanced voltage
Pending high freq.
Pending low freq.
Område
Kommentar
Brug spændingstransformer
ved højere spændinger
Brug altid strømtransformer
Description
AC-spænding indgang L1
AC-spænding indgang L2
AC-spænding indgang L3
Spændingsreferenceindgang
Strømtransformer indgang 1
Strømtransformer indgang 2
Strømtransformer indgang 3
Pump monitor (1-4)
Voltage missing
Voltage missing
Voltage missing
Alarm phase current missing
107
CA 443
DA
05/04/2022 12:18:56
05/04/2022 12:18:56