INSTALLATION INSTRUCTIONS - ENGLISH
PREPARING THE FIXTURE FOR INSTALLATION
1.Remove the parts pack and place it in a convenient location during
installation. Check that all parts are included.
2. Inspect the existing mounting location for damage before installing the
new CPHB LED high bay in this location. Ensure mounting structure is
properly sized to support the weight of the fixture.
3. Remove the fixture from packaging and inspect for any damages. Handle
fixture with care.
4. After installation ensure no wires are pinched or caught outside the
fixture housing.
INSTALLATION OF FIXTURE
• This fixture is designed to be Suspended using supplied V-Hangers and
Chain or Surface mount installation with optional Surface Mount Bracket
(THUN)- sold separately. Fixture may also be suspended using aircraft
cable (sold separately).
• Provide suitable hardware that is both in accordance with local codes
and is capable of supporting the full weight (7 lbs) of the fixture.
WARNING: Before wiring fixture to the power supply, turn off electricity at
fuse or circuit breaker box.
Suspended Installation- (Standard Mounting Method)
1) Locate provided Chains and V-Hangers. Attach Chain to each V-Hanger
by feeding hanger through chain link.
2) Attach the V-Hanger to fixture by hooking the hanger through holes on
the Fixture Housing- See Fig 2.
3) Secure the other end of the chain to structure using hardware rated for
the load.
Make sure the wiring hangers are fully engaged into the side holes on
the fixture housing. If using "S" hooks, make sure all loops are crimped
closed if possible.
Make sure wire hanger fits snuggly into holes of
fixture housing.
Supply Wire connections- Make all supply wire connections in
accordance with local electrical codes.
4) Remove access plate screw- see Fig 3 and remove access plate from
Fixture Housing (Input wires from Driver will be attached to the access
plate).
5) Remove the necessary knockout(s) from Access Plate.
6) Secure incoming power supply to access plate with UL Listed connector.
Use only UL listed supply wire (90°C or greater).
7) Make wire connections by connecting bare copper or green supply wire
to green fixture wire. Connect black supply wire to black fixture wire and
white supply wire to white fixture wire with UL Listed wire nuts (rated
90°C or greater). Purple and Pink leads are 0-10V (low voltage) dimming
leads and each wire shall be capped when not being used.
8) Reinstall Access plate and secure with access plate screw.
CCT/ALO Selection - if equipped
Locate the CCT and ALO Switches on fixture housing (see Fig 6).
Default CCT is set at 4000K and default light output is set at 18000lm
(ALO13) and 30000lm (ALO16). Slide switch to select desired CCT and
light output.
STEP-BY-STEP GUIDE
Surface Mount Installation- (Requires Surface Mount Bracket
(THUN) - sold separately
1) Attach THUN Surface Mount bracket(s) to structure using hardware
rated for the load.
2) Support fixture while snapping Fixture Housing into THUN bracket(s).
Ensure fixture is balanced.
3) Install supplied nut and lock-washer. Properly tighten nut to secure
THUN bracket around center channel- See Fig 4.
Pendant Monopoint Mount- (Requires Pendant Mount Bracket
(PMP)- sold separately
1) Attach PMP Hub to threaded pendant/conduit (not supplied) using 3/4"-
14 NPT THREAD HUB and Nut (supplied) as shown below.
2) Support fixture while snapping Fixture Housing into PMP bracket. Ensure
fixture is balanced.
3) Install supplied nut and lock-washer. Properly tighten nut to secure PMP
bracket around center channel- See Fig 5.
4) Connect the supplied flex conduit between the access plate KO and
PMP bracket KO. Connect input leads from fixture to one side of the
conduit inside the fixture. Connect power supply wires to other side of
the conduit in the PMP bracket. Make any necessary electrical connec-
tions. Supply wire must meet applicable electrical codes and be rated
for a minimum of 90°C. Pink and purple leads are 0-10V (low voltage)
dimming leads.
5) Attach PMP Bracket sides with screws, one each- See Fig 5. Ensure
wires are not pinched.
TROUBLE SHOOTING GUIDE
If this fixture fails to operate properly, use the guide below to diagnose
and correct the problem.
 Verify that fixture is wired properly.
 Verify that fixture is grounded correctly.
 The line voltage at the fixture is correct.
If further assistance is required, contact:
Technical Support: (800) 705-SERV (7378)
techsupport-industrial@acuitybrands.com
Limited Warranty and Limitation of Liability
5-year limited warranty. Complete warranty terms located at: www.
acuitybrands.com
Page 4

Publicidad

loading

Este manual también es adecuado para:

Cphb 12lm mvoltCphb 15lm mvoltCphb 18lm mvoltCphb alo13 mvolt sww9Cphb 24lm mvoltCphb 30lm mvolt ... Mostrar todo