Alarm Messages; Alarm Test - Selecta TEMPLOW L 2101280 Manual De Instrucciones

Armario congelador
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

MANUAL DE INSTRUCCIONES
Setting the delay time for the door open alarm
The time before the audible warning signal sounds after the door
has been opened can be adjusted.
Press
for 5 seconds. Display =
Press
until
appears in the display.
Press
. Display =
Setting range = 1 - 5 minutes.
Use button
or
to select the desired setting.
Press
. Display =
Press
for 5 seconds. The electronic control system will switch
back to normal operating mode.
Deactivating the audible warning signal function
The audible warning signal function can be completely deacti-
vated if necessary.
Press
for 5 seconds. Display =
Press
until
appears in the display.
Press
. Display =
Use button
or
to select the desired setting.
0 = activated
1 = deactivated
Press
. Display =
Press
for 5 seconds. The electronic control system will switch
back to normal operating mode.

Alarm test

This test checks the function of the internal and any external con-
nected alarm device. The appliance does not stop its refrigerating
function during this test.
Press
+
for 5 seconds.
• The display will change to a temperature value of 0.2°C below
the set upper alarm limit.
• The temperature value will now rise by 0.1°C every 2 seconds.
• When the upper alarm limit is reached, HIO will appear in the
display. An external alarm unit connected to the floating alarm
output will now be activated.
• The temperature value will continue to rise up to 0.2°C above
the upper alarm limit.
• The same process will take place automatically for the lower
alarm limit. LIO will appear in the display.
The LED
will be lit during the test.
The electronic control system will automatically switch back to
normal operating mode.
Cancelling the test prematurely
Press
for 5 seconds.
Note
If the values of the upper and lower alarm limit (AL and AH in the
section entitled "Adjusting the alarm parameters") are set to 0,
H-- and L-- will appear in the display during this test.
J
.P. SELECTA s.a.u.
CODIGO 80170 REV D
Autovía A2 Km 585.1 Abrera 08630 (Barcelona) España
e-mail: selecta@jpselecta.es - http://www.jpselecta.es

Alarm messages

1. LED
flashes in the display
If
appears in the display, the appliance has a fault. Consult
your nearest customer service point.
2. LED
flashes in the display; the display reads HI or LO
The interior is too warm (HI) or too cold (LO).
The audible warning signal sounds (unless the audible warning
signal function has been deactivated).
Note
The alarm parameters can be adjusted. See Adjusting the
alarm parameters.
3. HA /
flashes in the display
The interior was too warm or too cold (HA) during a certain period
of time.
Adjusting the alarm parameters
The alarm limits (difference to the set temperature) and the alarm
delay (delay until alarm sounds) can be adjusted.
Press
for 5 seconds. Display =
Press
until
appears in the display.
= Lower alarm limit
Press
. Display = temperature difference in °C
Use button
or
to select the desired setting.
Set positive values only.
Press
. Display =
Press
. Display =
Upper alarm limit
Press
. Display = temperature difference in °C
Use button
or
to select the desired setting.
Set positive values only.
Press
. Display =
Press
. Display =
Press
. Display = alarm delay in minutes
Use button
or
to select the desired setting.
Press
. Display =
Press
for 5 seconds.
The electronic control system will switch back to normal operat-
ing mode.
07/2020
Tel (34) 93 770 08 77 Fax (34) 93 770 23 62
Pag. 17
EN
17

Publicidad

Tabla de contenido
loading

Productos relacionados para Selecta TEMPLOW L 2101280

Tabla de contenido