RECEIVER
S7
NC
C
NO
ALLARME
NC/NO
ALARM
NC/NO
FAULT
CONDITIO-
C
OUT + F
E
N
+
G
-
A
B
Signalling Led
8
7
6
5
4
3
2
1
ON
1 2 3 4
S2 S3 S4
LD2
LD3
LD4
S7
RED
LD2
GREEN
LD3
YELLOW LD4
S6
S8
NC
C
OUT
NO
GUASTO
+F
Exchange of ALARM relay.
It is active about 40 seconds after smoke has been detected.
Act on jumper S7 in order to set the exchange C/NC or C/NO.
Exchange of FAULT relay.
It's active about 1 minute after the beam has detected a sudden
decrease of the signal under the minimum level.
N
Act on jumper S8 to set the exchange C/NC or C/NO.
It activates as the alarm relay. This output allows the direct connection of
the beam to one line of conventional fire control unit. During alarm the
resistence charge is 680 ohm.
Supplying positive 12 V
Supplying negative
Serial door for connection to optional module BR100
Module to visualize the signal:
–
during normal working, the display will visualize the unit values while the
Led bar will visualize the decimanl values of the signal received.
–
during alarm condition the letter A is visualized.
–
during fault condition the letter F is visualized.
-
during calibration the display visualizes the unit values whilst the Leds bar
visualizes the decimal values of signal received.
Module for visualization of detector condition:
S1
RED
LD2 OFF
GREEN LD3
YELLOW LD4 OFF
S8
OFF
ON
Slow flashing
Quick flashing
OFF
Quick flashing
ON
-
+
A
B
or 24 V
CALIBRATION MODE
OFF: if the signal of the Transmitter is not detected
ON: if the Receiver signal is detected
NORMAL MODE
Normal condition
Alarm
Normal condition (every 2 seconds)
With smoke exceeding the alarm threshold
Normal condition
Signal level under minimum (fault condition pre-alarm)
At the same time of fault relay activation
- 18 -
The terminal board is made of
two separate groups: the one
on the left concerns alarm and
fault-condition output whilst the
one on the right concerns
supplying input and serial door.
(min.11,5 V
/ max 27,8 V