INSTALLATION RULES
The beam and the reflector must be installed on plane wall, not subject to vibrations or deformation.
Please keep in mind these basic rules:
-
In order to obtain total coverage, the
distance (D) between more TX/
RX couples must not
exceed 15 meters.
-
distance from the walls
must be about the half of
the distance between
two beams (1/2 D).
-
distance from the ceiling (H)
must be between min. 40 cm.
and max 1 meter.
-
check the possibility of installing
reflectors in axis with beams.
1 mt
D
T X /
RX
In case of sloping roofs, install the first beam at H
distance from the highest side of the roof.
Install other beams maintaining distance D
between them and distance H from the ceiling.
Check to have the max distance of 1/2D
between the beam and the wall from the
lowest side of the roof.
Check
that
Receiv er
Transmitters can be installed on
the same axis.
H
In case of inclination of the roof, install the first beam at about 1 meter
from the highest wall and at H distance from the ceiling.
Install other beams maintaining distance D between
D
T X /
RX
T X /
RX
and
T X /
RX
1/2 D
- 21 -
1/2 D
D
T X /
RX
them and distance H from the ceiling.
Check to have max 1/2 D distance
between the beam and the lowest
1/2 D
side of the wall from the ceiling.
Check that Receiv er and
Transmitters can be installed
on the same axis.
T X /
RX
D
T X /
RX
H
T X /
RX
D
1/2 D
IST0675V2.2
E
N
G