Parameters for the chosen regulation type (only for winter operation)
• In case of "ON/OFF" regulation type,
the only parameter to be set is the
differential. Field (22) will display the
writing "dIF=" and on field (16) the
value currently set will flash. Press the
"
" and "
" keys to increase or
decrease the value. The range varies from
0.1°C to 1°C.
• In case of PROPORTIONAL regulation type, the parameters to be set are:
- regulation band
- regulation period
Field (22) will display the writing "bnd="
and on field (16) the value currently set
will flash. Press the "
to increase or decrease the value. The
range varies from 0.5°C to 5°C.
Once the band value is confirmed, field
(22) will display the writing "PEr=" and
on field (16) the value currently set will
flash. Press the "
to increase or decrease the value. It is
possible to choose between 10, 20 or 30
minutes.
For a wider description on how to operate the regulation type choice, please refer to
the chapter "REGULATION TYPE" on page 56.
" and "
" keys
" and "
" keys
- 49 -
ORUS RF Programmable Thermostat User Manual