5. Commissioning
Mode
Programming mode
(setting the parameters)
EN
Display mode
(normal operation, display
of pressure value)
5.3 Overview of parameters
Menu item
Description
SP1/SP2
Hysteresis function:
Switch point (switching output 1/2)
FH1/FH2
Window function:
Window high (switching output 1/2)
RP1/RP2
Hysteresis function: Reset point,
switching output (1 or 2)
FL1/FL2
Window function: Window low switch
output (1 or 2)
EF
Extended programming functions
RES
Return the set parameters to the factory
settings
DS1/DS2
Switching delay time, which must occur
without interruption before any electrical
signal change occurs (SP1, if applicable
SP2)
DR1/DR2
Reset delay time, which must occur
without interruption before any electrical
signal change occurs (RP1, if applicable
RP2)
10
Description
Activating the programming mode
Keep the "MENU" button pressed for approx. 2 sec. If the password is set to ≠ 0000, a password will be
requested. If authentication is successful, then it enters the programming mode, otherwise it reverts to
display mode.
Timeout
If, during the setting of a parameter, no button is pressed for 60 s, the instrument returns to the display
mode with the value unchanged.
Returning to the display mode
Simultaneous pressing of "INFO" and "MENU"
Parameter
0.25 ... 100 % of measuring range
0.25 ... 100 % of measuring range
0 ... (switch point - 0.25 % of measuring
range)
0 ... (window high - 0.25 % of measuring
range)
Yes/No
0.00 ... 65.00 s
0.00 ... 65.00 s
WIKA operating instructions pressure switch, model PSD-4
Factory setting
Nominal pressure
Nominal pressure
Nominal pressure -
10 %
Nominal pressure -
10 %
0.00 s
0.00 s