Descargar Imprimir esta página

IBEA IB-G3500 Manual Del Usuario página 35

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2. ELECTRICAL SAFETY PRECAUTIONS:
2.1. Electrical equipment including cable, cords and plug connection must not be
defective. Please check before using.
2.2. Do not plug the generator directly into a wall socket-outlet.
2.3. The generator should not be connected to other sources such as the power
company supply mains. In special cases where stand-by connection to existing electrical
systems or integration therewith is intended, note that it is a legal requirement that such
connections or integration may only be performed by a competent person.
2.4. Protection against electrical shock depends on circuit-breakers that are specially
matched to the generator. If a circuit breaker requires replacement, it shall be replaced
by a circuit breaker that has identical ratings and performance characteristics.
2.5. Due to high mechanical stress, only tough rubber-sheathed exible cable should be
used.
2.6. If the generator is of CLASS II construction, then earth of the generator is not
required.
2.7. Cord Extension Sets:
2.7.1.
A 1mm2 exible cable can draw a maximum of 10A provided that the cable is
not longer than 25m.
2.7.2.
A 1.5mm2 exible cable can draw a maximum of 10A provided that the cable is
not longer than 35m.
2.7.3.
A 1.5mm2 exible cable can draw a maximum of 16A provided that the cable is
not longer than 20m.
2.7.4.
A 2.5mm2 exible cable can draw a maximum of 10A provided the cable is not
longer than 65m.
2.7.5.
A 2.5mm2 exible cable can draw a maximum of 16A provided that the cable is
not longer than 45m.
2.7.6.
A 4mm2 exible cable can draw a maximum of 10A provided that the cable is
not longer than 100m .
2.7.7.
A 4mm2 exible cable can draw a maximum of 16A provided that the cable is
not longer than 65m.

Publicidad

loading

Productos relacionados para IBEA IB-G3500