The APS-412 switching power supply is designed for powering 12 VDC devices. It is provided with
a connector for integration with SATEL devices.
1. Description
Figure 1 shows the power supply enclosure.
F1 fuse (T 3.15 A) – AC circuit protection.
LEDs to indicate the power supply status:
– red LED:
OFF – current consumption not exceeding 4 A,
flashing – current consumption exceeding 4 A.
– yellow LED:
ON – battery OK or the battery testing mode disabled,
flashing – low battery (battery voltage below 11.5 V),
OFF – no battery or blown F3 fuse.
– green LED:
ON – AC power OK,
flashing – no AC power or blown F1 fuse.
Figure 2 shows the part of the electronics board visible after the cover is removed.
battery connector. The wires are included in the set (Fig. 3).
connector for supplying power to SATEL devices provided with a connector of the same type.
Additionally, information on the power supply status is transmitted via the connector. The cable
for connecting the power supply to a SATEL device is included in the set (Fig. 4).
F3 fuse (T 3.15 A) – protection of battery charging circuit.
DIP-switches. Used for configuring the power supply (see "Configuration").
Description of terminals
– terminal for connecting phase conductor.
L
– terminal for connecting neutral conductor.
N
– terminal for connecting protective conductor.
PE
+12V – +12 VDC power output.
COM – common ground.
– OC type output signaling 230 VAC power loss.
WS
– OC type output signaling low battery voltage (below 11.5 V).
WB
– OC type output signaling current overload (above 4 A).
WP
2. Configuration
The switch 6 must be set in OFF position.
The switches 1-5 are used for configuring the following power supply operating parameters:
Switch 1 – audible trouble signaling: ON=enabled / OFF=disabled.
Switch 2 – battery test: ON=enabled / OFF=disabled.
Quick installation guide
www.satel.eu.