SATEL
Switch 3 – battery charging current: ON=1 A / OFF=0.5 A.
The battery charging current must not exceed 10% of the battery capacity.
Switches 4 and 5 – AC power failure reporting delay: see table below.
Switch
4
5
3. Installation
Disconnect power before making any electrical connections.
Do not connect deeply discharged battery to the power supply (with voltage across
unloaded terminals below 11.5 V).
The used batteries must not be discarded, but should be disposed of in accordance
with the existing rules for environment protection.
The power supply should be permanently connected to the 230 VAC mains supply. Make sure that
the circuit you select will always be alive and protected with a proper safety device.
As the emergency power supply source, use a 12 V sealed lead-acid battery or other 12 V battery
with similar charging characteristics. The battery capacity must be selected to match the current
consumption in the system.
1. Remove the cover of power supply terminals (Fig. 5).
2. Use the DIP-switches (see Fig. 2) to configure the power supply.
3. If the connector for supplying power to SATEL devices is to be used, connect to it the cable
shown in Fig. 4 (Fig. 6).
4. If screw terminals are to be used for supplying power to devices, screw the wires to +12V and
COM terminals.
5. Connect the battery wires (Fig. 3) to the connector on the electronics board (Fig. 7).
6. You can connect the trouble signaling outputs with control panel zones, or you can connect e.g.
LEDs to these outputs.
7. Run the 230 VAC power cable through the cable gland (Fig. 8).
8. Screw the 230 VAC power wires to terminals: phase conductor to L terminal, neutral conductor to
N terminal, and protective conductor to PE terminal (Fig. 9).
9. Screw the element fastening the 230 VAC power cable (Fig. 10).
10. Replace the cover of power supply terminals (Fig. 11) and fasten it with a screw (Fig. 12).
11. Connect the battery to the dedicated wires (battery positive to red wire, negative – to black).
12. Turn on 230 VAC power. When the AC power is present, the power supply will signal it with
a single beep sound and the
If the power output is shorted to common ground or the F3 fuse is defective, the power supply
will turn off.
The declaration of conformity may be consulted at www.satel.eu/ce
APS-412
AC power failure reporting delay
3 s
60 s
OFF
ON
OFF
OFF
LED turning ON.
600 s
1800 s
OFF
ON
ON
ON
7