BRAUKMANN FK06 DIALSET®
1
LOOSEN THE SETPOINT DIAL LOCKING SCREW.
2
UNSTRESS THE
PRESSURE SPRING
BY TURNING COUNTER-
CLOCKWISE
.
3
UNSCREW THE BONNET WITH A 1-5/8" WRENCH.
4
REMOVE CARTRIDGE USING A PLIERS AS A LEVER.
6
REASSEMBLE BONNET IN REVERSE ORDER.
Fig. 4. Replacing the FK06 cartridge.
38-00059EFS—11
1-5/8 WRENCH
WHEN REASSEMBLING,
5
ENSURE O-RINGS AND
WASHER ARE PROPERLY
INSTALLED
WASHER
(LIP UP)
O-RINGS
Cleaning
CAUTION
Do not use any cleansers that contain
solvents and/or alcohol for cleaning
the plastic parts.
If necessary, the filter bowl and the filter can
be cleaned.
Frequency: every 6 month (depending on
local operating conditions)
To be carried out by an installation company.
Detergents must not be allowed to enter the
environment or the sewerage system!
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g.
through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
• Use double ring wrench ZR06F
5. Remove filter, clean and reinsert
6. Place O-ring onto filter bowl
7. Screw in filter bowl hand-tight (without
tools)
8. Slowly open shutoff valve on inlet
9. Slowly open shutoff valve on outlet
DISPOSAL
• Dezincification resistant brass housing
• Brass connections
• High-quality synthetic material valve
insert
• High-quality synthetic material spring
bonnet with adjustment knob and setting
scale
• Spring steel adjustment spring
• Stainless steel fine filter
• Shock-resistant, clear transparent
synthetic material filter bowl
• Fibre-reinforced NBR diaphragm
• NBR seals
M36658A
NOTE:
Observe the local requirements
regarding correct waste recy-
cling/disposal!
6