Descargar Imprimir esta página

Seko WAREDOSE 35 Manual De Instalación página 8

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

EN
WAREDOSE 35
Picture 5
* Installation suggested using plastic T connector
Always use the foot filter and make sure that it reaches the bottom of the tank. Periodically clean it
from possible residues.
INPUT – OUTPUT
3.
3.1 User Interfaces:
1 x 16 digit LCD display with backlight
3 buttons for programming
3.2 Input connections:
3 PG7 for optional Connections
1 hole with 21 mm diameter with flexible conduit fitting 1 small cable gland for the level probe connection.
NOTE: The plastic corrugated pipe to be used needs to have 20 mm external diameter.
3.3 Input on the board
100-240 Vac main Power Supply
Opto-insulated Signal Inputs S1, S2, S3: FIRST CHARGE, RINSE, WASH
accepting every Voltage from 12 Vac up to 240 Vac.
Conductivity Probe Input
2 Level probe inputs, Normally Open
3.4 Output on the board
1 Alarm output (24 VDC) will be available in case of alarm, for an external low power lamp or buzzer
(500mW max).
0000138112
6 mm OD PE tube
T connector
non return injection valve
metal band
rev. 1.0
6

Publicidad

loading