The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.5m, then additional charge after
vacuuming is not necessary. If the piping length is more than 7.5m, then use the additional charge value as indicated in
the table.
Additional refrigerant charge [g] per additional 1m length as tabulated
Indoor (ATXN)
Outdoor (ARXN)
Additional charge [g/m]
Example:
ATXN25 & ARXN25 with 12m piping length, additional piping length is 4.5m.
Thus, Additional charge = 4.5[m] x 20[g/m]
IR Signal Receiver
When an infrared remote control operating signal has been
transmitted, the signal receiver on the indoor unit will respond
as below to conf rm acceptance of the signal transmission.
ON to OFF
OFF to ON
Pump down / Cool force on
Others
Cooling Unit/Heat Pump Unit
The table shows the LED indicator lights for the air conditioner
unit under normal operation and fault conditions.
The LED indicator lights are located at the side of the air
conditioner unit.
The heat pump units are equipped with an "auto" mode
sensor whereby it will provide reasonable room temperature
by switching automatically to either "cool" or "heat" mode
according to the temperature set by the user.
LED Indicator Lights: Normal Operation And Fault Conditions For Cooling/Heat Pump Unit
MV/JX
COOL/HEAT
(GREEN/RED)
GREEN
RED
RED
GREEN
GREEN
GREEN
RED
GREEN
ON
ADDITIONAL CHARGE
25
25
20
= 90.0[g]
INDICATOR LIGHTS
1 Long Beep
2 Short Beep
1 Short Beep
NV
COOL/HEAT
(BLUE/RED)
BLUE
RED
RED
BLUE
BLUE
BLUE
RED
BLUE
Blinking
35
35
20
LED Indicator Lights for Cooling Unit/Heat
Pump Unit
ON/OFF
Model
Operation
Cool mode
Heat mode
Auto mode in Heating operation
Auto mode in Cooling operation
Timer on
Sleep mode on
Fan mode on
Dry mode on
Defrost operation
Unit error
1-14
50
60
50
60
20
20
IR
Receiver
IR Receiver
Cool/Heat
Timer
Sleep
ON/OFF switch