WARNING: Do not bypass the blocked flue switch. To do so could expose the consumer to property
!
damage, personal injury or possible death.
FIG. 3
10' or Less
2' Min.
Chimney
FIG. 4-A
Switch/
Gas
Control
Wire
GAS-FIRED VENTED WALL FURNACE
INSTALLATION SECTION
ROUGH-IN INSTRUCTIONS
Height above any
More than 10'
roof surface within
10' horizontally
10'
2' Min.
3' Min.
Chimney
3' Min.
Man. Reset
Blocked
Flue Switch
Draft
Diverter
Relief
Opening
Combustion
Chamber
NOTE: MAXIMUM WALL THICKNESS FOR A DUAL WALL
(W505, W506) INSTALLATION IS 5-3/8".
STEP 1.
Attach the base plate (purchased with the vent pipe) to the
header plate using two No. 8 sheet-metal screws through
the pre-punched holes. The heater may not vent properly
without a base plate to anchor and seal the vent system.
See Figure 6 (on page 10).
FIG. 4-B
Reset
Button
Page 9
FIG. 5: Gas Supply
To Heater Gas
Control Valve
Manual Cut-Off-Valve
1/8" NPT
Pressure Tap
Drip Leg
Gas
Supply
Line
1017754-A