Ajuste eléctrico carel para bombas de calor condensadas con aire con compresor scroll de alta eficiencia
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

WORKING THERMOSTAT
The following designs show how the micro
chiller controller calculates the machine's
intervention level, according to the working
settings fixed by the user (the procedure for
modifying and the list of parameters that
can be modified are shown on the previous
pages).
Key::
Po: Power rendered
TIA: Water inlet temperature
r1: cold setting
r2: differential in cold mode
r3: hot setting
r4: differential in hot mode
STANDARD CALIBRATION AND CALIBRATION FIELD OF REGULATING DEVICES
Water temperature set to heating
Differential working thermostat in heating
Water temperature set to cooling
Differential working thermostat in cooling
6
Cold thermostat at a level
Po
100 %
0 %
Set
r1
Hot thermostat at a level
Po
100 %
0 %
r4
ON
OFF
r2
ON
OFF
r3
U.M.
MINIMUM
°C
25
°C
0,3
°C
7
°C
0,3
TIA
TIA
Set
recovery
MAXIMUM
hole
46
55
2
19,9
11
25
2
19,9