Parameter
Delta control
XXX.X [bar]
Hz
Freq.min.control
Min mot. freq
Delta start
XXX.X [bar]
Delta stop
XXX.X [bar]
Ki
Kp
Pump DOL 1
ON/OFF
Pump DOL 2
ON/OFF
COMBO
ON/OFF
Default
Value drop below the set value required
0.1
to restart the pump during control ramp.
Delta control
Stop delay
Value drop below the set value required
0.5
to start the pump from stop condition.
Value increase respect to set value which
0.5
must be passed so that there is a forced
shutdown of the pump.
Kp and Ki parameters allow the dynamic
control of system by IPFC; set values
(Ki=50, Kp=005) are usually enough to get
a valid dynamic control.
Function to activate (ON) the first
auxiliary pump DOL 1 (Direct On Line
OFF
pump).
Function to activate (ON) the second
auxiliary pump DOL 2 (Direct On Line
OFF
pump).
Enabling or disabling COMBO operation
OFF
as described in COMBO chapter.
Description
Control ramp
press.
Set value
sec
25