Descargar Imprimir esta página
Circutor P11941 Guia De Inicio Rapido

Circutor P11941 Guia De Inicio Rapido

Relé de protección diferencial electrónico

Publicidad

Enlaces rápidos

Código
code
P11941
P119410006000
DESCRIPCIÓN GENERAL
- Dispositivo con 2 relés programables independientes, canal principal y canal de prealarma.
- Dispone de 2 salidas. Disparo de relé principal y la de señalización por prealarma.
- Dispone de 1 entrada libre de potencial para realizar un Disparo/Rearme exterior.
- Montaje en Carril DIN 46277 (EN 50022) o en panel 72x72 mediante accesorio (M5ZZF1)
- Asociado a transformador de corriente diferencial externo serie WGC
- Comprueba conexión con transformador exterior WGC mediante test inductivo.
- La detección y medida de la fuga se realiza calculando su verdadero valor eficaz (TRMS).
- Visualización por display de los valores de ajuste y de la corriente de fuga instantánea.
CONSIDERACIONES INICIALES
COMPROBACIONES A LA RECEPCIÓN
Asegurarse del cumplimiento de:
- El equipo corresponde a las especificaciones de su pedido.
- El equipo no ha sufrido desperfectos durante el transporte.
Para más información puede descargarla de nuestra web, www.circutor.es.
PRECAUCIONES DE SEGURIDAD
Para la utilización segura del equipo, es fundamental que las personas que lo instalen o
manipulen, sigan las medidas de seguridad habituales, así como las advertencias en
dicha guía rápida.
El RGU-10 es un equipo diseñado específicamente para ser instalado dentro de un cuadro
-
eléctrico o envolvente, con fijación en carril DIN o en panel mediante accesorio. Dispone
de led luminoso (ON) indicando que hay presencia de tensión. Aunque este led no esté
encendido, no exime al usuario de comprobar que el equipo está desconectado de toda
fuente de alimentación.
A su vez, el circuito de alimentación debe estar provisto de un interruptor magnetotérmico
o dispositivo equivalente para desconectar el equipo de la red de alimentación.
INSTALACIÓN Y PUESTA EN MARCHA
La presente guía rápida contiene información y advertencias que el usuario
tiene que respetar para garantizar el funcionamiento seguro del equipo. En su
funcionamiento habitual no debe ser utilizado hasta su instalación definitiva en
el cuado eléctrico.
¡IMPORTANTE!
Si se utiliza el equipo de forma no especificada por el fabricante, la protección
puede resultar comprometida
Cuando sea probable que el equipo haya perdido la protección de seguridad (presencia
de daños visibles) debe desconectarse la alimentación del equipo. En este caso póngase
en contacto con el servicio técnico cualificado, o bien, con nuestro S.A.T. (Servicio
Asistencia Técnica).
PRECAUCIONES DE SEGURIDAD
La instalación es en carril DIN. Por el toroidal asociado tienen que pasar todos los
conductores activos que alimentan a las cargas o parte de la instalación en la que se
requiera realizar la protección diferencial con este equipo. En instalación monofásica
(fase y neutro, L y N), trifásica (las tres fases, L1,L2 y L3) o trifásica mas neutro (L1, L2, L3
y N). El equipos debe montarse en el interior del cuadro eléctrico. A tener en cuenta, que
con el equipo conectado, los bornes y la apertura de cubiertas o eliminación de
elementos, puede dar acceso a partes peligrosas al tacto.
El equipo no debe ser utilizado hasta que haya finalizado por completo
su instalación. El equipo debe conectarse a un circuito de
alimentación protegido con fusibles acorde con el rango de
alimentación y consumo del mismo. A su vez el circuito de
alimentación tiene que estar provisto de un interruptor
magnetotermico o dispositivo equivalente para desconectar el equipo
de la red de alimentación. En el conexionado se aconseja una sección
2
cable permitida entre 1- 1.5 mm. Un par de apriete recomendado de
0,5-0,6 N.m y una longitud a desaislar cable de 7 mm.
BORNES DE CONEXIONADO
DESCRIPCIÓN DE BORNES
1-2
Entrada disparo externo
3
Sin uso
4
Contacto salida relé prealarma común.
5
Contacto salida relé prealarma NC
6
Contacto salida relé prealarma NA
7
Sin uso
8
Entrada toroidal 1S2
9
Entrada toroidal 1S1
10
Alimentación Aux (fase o neutro)
11
Alimentación Aux ( neutro o fase)
12
Sin uso
13
Contacto salida relé disparo NA
14
Contacto salida relé disparo NC
15
Contacto salida relé disparo COMUN
M98200901-20-21A
Relé de protección diferencial electrónico RGU-10
RGU-10 Electronic Earth-leakage Protection Relay
Sensibilidad (A)
Tipo
Type
Sensivity
0,03-0,1-0,3-0,5-1-3
por ajuste directo
RGU - 10
by direct setting
5-10-30 por/by SETUP
Por ejemplo RGU-10 alimentado a 110 V c.a / For instance RGU-10
52,5
Fixed by rail DIN /
Fijación carril DIN 46277 (EN 50022)
Peso/Weight :168 gr
CARACTERÍSTICAS
Optoacoplada
Corriente Nominal: 6 Ac.a.
Tensión Nominal:
230 Vc.a.
Corriente Nominal: 6 Ac.a.
Tensión Nominal:
230 Vc.a.
Retardo disparo (s)
Tripping delay
INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
por ajuste directo / by direct setting
3-5-10 por/by SETUP
GENERAL DESCRIPTION
- Device with 2 independent, programmable relays, one main relay one prealarm.
- It has 2 outputs. Main trip relay and prealarm signal relay.
- It has 1 potential free input for external ON/OFF.
- Mounting in DIN rail 46277
- Associated to a WGC Series external, toroidal current transformer.
- It verifies connection with external transformer WGC by inductive tests.
- Leakage detection and measurement is via calculating its true effective value (TRMS)
- Displays setting values and instant current different to its associated units
PRELIMINARY CONSIDERATIONS
CHECKS ON RECEPTION
On receving the instrument, check the following points:
- The unit's specifications are the same as those on your order.
- Check that the device has not suffered any damage during transport.
You can download more information from CIRCUTOR website, www.circutor.es
SAFETY PRECAUTIONS
The staff using or handling the unit must follow the common safety measures and
warnings included in the instruction manual.
The RGU-10 unit has been specifically designed for its installation in a electric board,
enclosure to a DIN rail or mounted in panel by means of accesories. It has a flashing
green led (ON) when it is operation and, therefore, it shows that there is voltage and
current in the electronic circuit. The user must make sure that the equipment is not
conected to the power supply at all the times, even when the LED is not flashing.
Likewise, the power supply circuit must have a built-in cicuit breaker or equivalent device
to disconnect the unit from the power.supply network.
INSTALLATION AND START-UP
The user must take into account and observe the informations and warnings included in
this instruction manual to guarantee the correct operation of the equipment and comply
whit the safety specifications. The equipment must not turned on until is fully installed in
the electrical panel.
The unit´s protections systems might not be effective if the unit is used for
purpose other than those specifications by the manufacturer.
Disconnect the equipment from the power supply when the unit´ssafety protection
systems are not working or there are signs of a problem (in case of visible damage). In this
case, contact a qualified technical service or with our own technical service (TAS).
PRECAUCIONES DE SEGURIDAD
DIN rail installation. Through the CBT must pass all live conductors supplyng electrical
energy to loads or part of the installation which requires it to earth leakage protection with
this device. In single-phase installation (phase and neutral, L and N), three phase - 3
wires (three phases, L1, L2 and L3) or three phases - 4 wires (L1, L2, L3 and N). All
connections should be inside the electrical board. Please note that with the connected
equipment, terminals and opening covers or removing elements, can give access to
67,9
43,5
TERMINAL CONNECTIONS
TERMINAL DESCRIPTION
1-2
External Input Trip/ Reclose
3
Not used
4
Pre-alarm output relay common
5
Pre-alarm output relay, NC
6
Pre-alarm output relay, NA
7
Not used
8
Input C.B.T. 1S2
9
Input C.B.T. 1S1
10
Supply 230 Va.c (Phase or Neutral)
11
Supply 230 Va.c (Neutral or Phase)
12
Not used
13
Tripping output relay NO
14
Tripping output relay NC
15
Tripping output relay COMMON
P 1 X X X X 0 0 X
Comunicaciones
Communications
Código
Código interno
Code
Tensión de
No disponible
alimentación
Not available
Power supply
supplied by
110 V a.c...
or PANEL 72x72 by means accesories (M5ZFF1)
(EN 50022)
¡IMPORTANTE!
IMPORTANT!
dangerous parts to touch. The equipment must not be used
until it has completely finished installation. The unit must be
connected to a power supply circuit protected by fuses in
line with the range and power consumption. In turn, the
supply circuit must be provided with a circuit breaker or
equivalent device to disconnect the equipment from the
mains. During the wiring cable is advisable a section
2
permitted between 1 - 1.5 mm. A recommended torque of
0.5-0.6 N.M. Cable Stripping Tools length 7 mm.
Internal code
0
230 V c.a.
1
110 V c.a.
24/ 48 V c.a/a.c
4
24/120 V c.c/d.c
P11941001
.
FEATURES
Optocoupled
Rated current: 6 Ac.a
Rated voltage : 230 Vc.a
Rated current: 6Ac.a.
Rated voltage: 230 Va.c
Pag. 1/4

Publicidad

loading

Resumen de contenidos para Circutor P11941

  • Página 1 - El equipo no ha sufrido desperfectos durante el transporte. - Check that the device has not suffered any damage during transport. Para más información puede descargarla de nuestra web, www.circutor.es. You can download more information from CIRCUTOR website, www.circutor.es...
  • Página 2 Relé de protección diferencial electrónico Series RGU-10 Electronic earth-leakage protection Relay RGU-10 Series DESCRIPCIÓN DE LOS LED Y PULSADORES DESCRIPTION LEDS AND BUTTONS - Shows equipment status via a display and 2 LED's. - Indicación del estado del equipo mediante display y 2 LED. - Ajuste y programación del equipo mediante 5 pulsadores.
  • Página 3 - Safety: CAT III (EN61010) Nota: Circutor garantiza que el equipo RGU-10 cumple con un tiempo de respuesta Note: Circutor guarantees that the RGU-10 device complies with a response time of inferior a 30 ms a 5In, y en combinación con el elemento de corte seleccionado se deberá...
  • Página 4 Support Service. Tel: 902 449 459 (Spain) Tel: 902 449 459 (España) Tel: (+34) 93 745 29 00 (Out of Spain) Tel: (+34) 937 452 919 (Fuera de España) Email:sat@circutor.com Email:sat@circutor.com Vial Sant Jordi s/n Vial Sant Jordi s/n Www.circutor.com www.circutor.es...

Este manual también es adecuado para:

P119410006000Rgu - 10