Descargar Imprimir esta página

SJE VFDC-4100 Manual De Instrucciones página 15

Publicidad

Idiomas disponibles

Idiomas disponibles

3.2.8 System Setup
Menus
Setup Menu
RETURN MAIN SCREEN
LCD BACK LIGHT TIME
DATA LOG
SYSTEM
TEST CODE
SET UP
RELAY OUTPUT 1-5
DIGITAL OUTPUT 6-13
LANGUAGE
PRESS UNIT
3.2.9 Communication Setup (RS-485)
Menus
Setup Menu
PARITY
COMM
BAUDRATE
SETUP
NODE
DATA BITS
STOP BIT
3.2.10 Communication Setup
Menus
Setup Menu
SCHEDULE OPERATION
00:00:00 ~ 00:00:00
PROGRAM
TUESDAY
FEBRUARY
SJE ®
Contents
Returns to the main screen after set time if user
does not use any key controls
After the set time, LCD back light automatically turns
off. This can be disabled by setting value to 999.
Sets the sampling rate for the Operation data log
Internal code to check the system.
Relay output 1-5 allows for up to 5A @ 250V
Digital output is transistor out. High = 5V Low = 0V
Available settings for outputs are: NOT USED,
PUMPS STOPPED, PUMPING, GENERAL ALARM,
LOW SUCTION, P1-P4 VFD RUN, P1-P4 ATL RUN,
BUZZER, LOW PRESSURE, HIGH PRESSURE,
VFD 1-4 FLT/HOA, SENSOR FAULT
Language selection
Unit of measure for analog input
Contents
Select parity mode
Transmission speed
Network node address
Contents
This function allows the set pressure to be
adusted based on a schedle. If on certain days
of the week, you wanted the set pressure to be
different, you would set schedule operation to
WEEKLY then set the pressures for the days of
the week.
13
Input Range
10 ~ 300
10 ~ 999
10 ~ 999
0 ~ 9999
English/Espanol
PSI/BAR
Input Range
EVEN, ODD, NONE
9600, 14400, 19200
1~31
8
1,2
Input Range
NOT USED, TIMELY, WEEKLY,
MONTHLY
VFDC-4100 Controller User Manual

Publicidad

loading

Productos relacionados para SJE VFDC-4100