2.3 Default Values
Menus
YEAR
MONTH
DATE
DATE
WEEKDAY
TIME
HOUR
MINUTE
SECOND
LEAD PUMP
PUMP 1
PUMP
PUMP 2
SET UP
PUMP 3
PUMP 4
LIMIT TOTAL PUMPS
SET PRESSURE
SET PRESSURE 2
HIGH PRESSURE LIMIT
PRESSURE
LOW PRESSURE LIMIT
SET UP
START LEAD PRESSURE
START LAG PRESSURE
STOP LAG PRESSURE
P VALUE
I VALUE
D VALUE
CYCLE TIME
ALTERNATION
FRICTION
CONTROL
RUN DELAY
SET UP
STOP DELAY
JOCKEY STOP DELAY
OPERATION TYPE
LOW SUCTION TMR
LOW SUCTION RST
LOW SUCTION RST TMR
LOW PRESSURE STOP TIME
INITIALIZE
SENSOR
SENSOR VALUE
SET UP
SENSOR OFFSET
VFD STOP TIME
VFD MINIMUM RATE
VFD STOP RATE
VFD
VFD DISP. TYPE
VFD AUTO RESET
PIPE FILL
PIPE FULL RATE
PIPE FILL TIMER
SJE ®
Setup Menus
Default
2004
1
1
0
0
0
0
PUMP 1
USED
USED
NOT USED
NOT USED
NO
60 PSI
60 PSI
95 PSI
15 PSI
-3 PSI
-7 PSI
3 PSI
60
30
1
120 Msec.
24 HOURS
0.0 PSI
1 SECONDS
1 SECONDS
5 SECONDS
VFD
30 SECONDS
AUTO
30 SECONDS
10 SECONDS
200 PSI
0 PSI
30 SECONDS
40%
60%
100%
5
OFF
45%
30 SECONDS
6
Input Range
0000 ~ 9999
1 ~ 12
1 ~ 31
MONDAY ~ SUNDAY
0 ~ 23
0 ~ 59
0 ~ 59
1 ~ 4
USED, NOT USED, JOCKEY
USED, NOT USED
USED, NOT USED
USED, NOT USED
NO, YES
2 PSI ~ 650 PSI
2 PSI ~ 650 PSI
3 PSI ~ 719 PSI
1 PSI ~ 649 PSI
-65 PSI ~ 65 PSI
-65 PSI ~ 65 PSI
-0 PSI ~ 65 PSI
0 ~ 200
0 ~ 200
0 ~ 200
50 ~ 999 M.SEC.
0 ~ 999 HOURS
0 ~ 650 PSI
0 ~ 10 SECONDS
0 ~ 999 SECONDS
0 ~ 999 SECONDS
VFD, 1VFD+ATL
10 ~ 999 SECONDS
AUTO, MANUAL
10 ~ 9999 SECONDS (2.78 HOURS)
10 ~ 999 SECONDS
YES, NO
29 PSI ~ 720 PSI
-72 PSI ~ 72 PSI
0 ~ 60 SECONDS
10 ~ 90 % (of VFD DISP. TYPE)
20 ~ 90 (of VDF DISP. TYPE)
100%, 60Hz, 50Hz
0 ~ 20
ON, OFF
10 ~ 90% of VFD DISP. TYPE or VFD
5 ~ 600 SECONDS
VFDC-4100 Controller User Manual