Custom Energy Savings Settings
05 – INCIDENTAL OCCUPANCY THRESHOLD
(00 - 60; 05* default setting) Select the minimum period of
time (in minutes) for which occupancy needs to be detected
to enter the guest occupancy mode.
When occupancy is detected, thermostat will switch to
occupied mode for a duration of "Incidental Occupancy
Threshold" selected here.
If occupancy is detected for a period of time shorter than
the "Incidental Occupancy Threshold" selected here, the
thermostat will automatically revert to unoccupied mode at
the end of the "Incidental Occupancy Threshold" period and
continue to observe energy saving functions that were in
effect before the room became occupied. This setting allows
ignoring incidental room visits.
If occupancy is detected for a period of time longer than
the "Incidental Occupancy Threshold" selected here, the
thermostat will enter the guest occupancy mode. When the
thermostat is in the guest occupancy mode, it will revert
to unoccupied mode and initiate the setback temperature
only when occupancy is not detected for the duration of the
setback delay (Heat or Cool) period.
25
49-5000416 Rev. 1