WIRING INSTRUCTIONS (Hardwired)
Route the HCS conduit to a nearby junction box. Use the included
½" trade size watertight conduit fitting and sealing washer to
provide a moisture-resistant seal between the conduit fitting
and the junction box. If necessary, drill a ⅞" diameter hole to
accommodate the conduit fitting. For outdoor installations, ensure
the junction box is fully sealed using appropriate electrical grade
silicone sealant.
Figure 6: Wiring the
EVSE in a Junction
Box
Before connecting the service
conductors, please carefully read the
section of this manual titled Installation -
Service Connections. If unsure of the type
of power provided at the service panel,
please consult with the local utility or
call a Service Representative for
assistance.
The three supplied HCS-40 service
conductors use stranded 10 AWG 90ºC
copper wire.
The three supplied HCS-50, HCS-60, and
HCS-80 service conductors use stranded 8
AWG, 90ºC copper wire.
The insulation of each conductor is color
coded for standard 240V AC installation:
Green:
Ground
Black:
Line 1 (120V AC to Ground)
Red:
Line 2 (120V AC to Ground)