EN
Parameter setting instructions
Setting and parameterization
Use the [MODE] or [SET] touchpads to navigate through the main menu (fig. 5), as well as the
OUT1 and OUT2 submenus (fig. 6), the EF extended functions menu (fig. 7) or the DISP display
menu (fig. 8). Press [ENTER] to select the respective submenu. Touching [MODE] and [SET]
at the same time will cancel the parameter assignment. The device returns to the standard
display.
NOTE
For parameterization in legacy mode, refer to the instructions for use document numbered
100003050.
Locking the device
Touch and hold [MODE] and [SET] simultaneously for 3 s.
f
While the LOC LED is flashing, Loc appears on the display and then disappears.
B
B
The LOC LED lights up yellow.
If the sensor touchpads are not actuated for 1 min, the sensor is locked automatically.
Unlocking the device
Touch and hold [ENTER] for 3 s until all of the bars flash green.
f
Swipe [MODE], [ENTER], [SET] in succession: Two red flashing bars appear when each touch-
f
pad is touched. Swipe the nearest touchpad once the two red bars turn green.
f
Release the touchpads when six green bars are flashing on the display.
The LOC LED goes out.
B
uLoc appears in the display and then disappears.
B
Setting parameter values via the touchpads
If the LOC LED lights up and a red running light is shown on the display when [MODE] or
f
[SET] is touched, unlock the device.
Touch [MODE] or [SET] until the required parameter is displayed.
f
Touch [ENTER] to select parameters (fig. 5).
f
Changing the displayed value: Touch and hold [SET] for 3 s until the display stops flashing.
f
Or: Touch [MODE] to return to the parameter selection.
Increase or decrease the value gradually via [MODE] or [SET]. Certain values can be continu-
f
ously changed by touching and holding [MODE] or [SET] (fig. 5).
Touch [ENTER] to save the modified value. The saved value flashes twice.
f
Protecting the device with a password
Select PASS in the EF menu.
f
Change values via [SET].
f
Use the [MODE] touchpad to navigate between the digits of the four-digit password (fig. 9).
f
Touch [ENTER] to save the new password.
f
Parameters in the main menu
Default values are shown in bold.
Explanation
Function
OUT1
Output 1
Switching output 1 setting options
submenu
OUT2
Output 2
Output 2 setting options
submenu
DISP
Display
Refer to the "Parameters in the DISP submenu" table for additional
submenu
setting options
EF
Refer to the "Parameters in the EF submenu" table for additional
Extended
Functions
setting options
submenu
Hans Turck GmbH & Co. KG | Witzlebenstraße 7, 45472 Mülheim an der Ruhr, Germany | Tel. +49 208 4952-0 | Fax +49 208 4952-264 | more@turck.com | www.turck.com
Parameters in the OUT... (outputs) submenu
Explanation
Options
Function
OTYP
Output Type
SSP
Switching output
(OUT2)
AnA
Analog output
MODE
OFF
SPM
Single point mode
WIn
Window mode (window function)
TPM
Two point mode
SP1
Switching
SPM: Limit value at which the switching output
point 1
changes its switching state
TPM: Upper limit value at which the switching output
changes its switching state as the temperature rises
WIn: Upper window limit at which the switching out-
put changes its switching state
Default: 80.0 °C
SP2
Switching
SPM: Not available
point 2
TPM: Lower limit value at which the switching output
changes its switching state as the temperature falls
WIn: Lower window limit at which the switching output
changes its switching state
Default: 70.0 °C
HYST
Hysteresis
The minimum hysteresis is 0.1 K.
The maximum hysteresis comprises the complete value
range of the sensor.
Default: 0.1 K
LOGI
Invert switching
HIGH
0  1
logic
LOW
1  0
P-n
Behavior of
AUTO
Automatic detection (NPN/PNP)
the switching
PnP
N switching
output
nPn
P switching
FOU
Behavior in the
on
Switching output:
event of a fault
The output is activated in the event of an error.
(e.g. wire break
or short circuit)
Analog output:
Error value of the set function at output 2 (OUT2)
OFF
Switching output:
The output is deactivated in the event of a fault.
Analog output:
Error value of the set function at output 2 (OUT2)
Don
Switch-on delay
0...60 s in increments of 0.1 s
(0 = delay time not active)
Default: 0.0 s
DOFF
Switch-off delay
0...60 s in increments of 0.1 s
(0 = delay time not active)
Default: 0.0 s
AMOD
Analog output
AUTO
Automatic detection (4...20 mA/0...10 V)
(OUT2)
4–20
4...20 mA
0–20
0...20 mA
20–4
20...4 mA
20–0
20...0 mA
0–10
0...10 V
0–5
0...5 V
1–6
1...6 V
10–0
10...0 V
5–0
5...0 V
6–1
6...1 V
0545
0.5...4.5 V
4505
4.5...0.5 V
ASP
Start point of
Temperature value at which the analog output signal
the analog
has its start point
signal
Default: -49.9 °C
AEP
End point of the
Temperature value at which the analog output signal
analog signal
has its end point
Default: 50.0 °C
Parameters in the DISP submenu (Display)
Explanation
Options
Function
DISr
Display
Display rotated by 0°
orientation
180°
Display rotated by 180°
DISU
Display
50
50-ms update time
update
200
200-ms update time
600
600-ms update time
OFF
Display update deactivated
coLr
Display color
GrEn
Always green
rED
Always red
G1oU
Green if OUT1 is switched, otherwise red
r1oU
Red if OUT1 is switched, otherwise green
G2oU
Green if OUT2 is switched, otherwise red
r2oU
Red if OUT2 is switched, otherwise green
G-CW
Green if the measured value is between the switching
points CSP1 and CSP2
r-CW
Red if the measured value is between the switching
points CSP1 and CSP2
DUA
Display
OFF
Display of temperature value
on
Alternating display of temperature value and unit
CSP1
Virtual upper
Upper switching point at which the display changes
switching point
color
(if display color G-CW or r-CW is selected)
Default: 80.0 °C
CSP2
Virtual lower
Lower switching point at which the display changes
switching point
color
(if display color G-CW or r-CW is selected)
Default: 70.0 °C
Parameters in the EF submenu (Extended Functions)
Explanation
Options
Function
Semo
Set mode
SSP
Smart Sensor Profile
LEGA
Legacy Mode
COF
Offset adjust-
Severe temperature changes in the environment of
ment
the sensor can cause the shifting of the zero point. As a
result, the measured value zero is not displayed at 0 °C .
This drift can be corrected with the offset value.
Setting range: -55...+55 °C in increments of 0.1 K.
Default: 0.0 
UnIT
Display unit
°C
°C
°F
°F
K
K
Ω
Ohm
HI
Maximum value
The highest process temperature is stored and
memory
displayed.
Lo
Minimum value
The lowest process temperature is stored and dis-
memory
played.
OPHr
Operating hours
Display of operating hours in years (y), days (d) and
counter
hours (h)
PASS
Password
Define password and activate password protection
0000
No password
SOF
Software ver-
Display of the firmware version
sion
rES
Reset
FACT
Reset the parameters to factory settings
rEBO
Restart the device (warm start)
APPL
Reset application-specific data
HIGH
Reset the maximum value memory: The highest pro-
cess temperature is deleted.
LOW
Reset the minimum value memory: The lowest process
temperature is deleted.
UnDO
Reset the parameters to the previous settings (last
device start)
EF menu
5
S
S
E
>3 s
Current value
M
S
Semo
SSP
LEGA
E
Save value
M
S
M
COF
S
M
S
E
>3 s
Current value
M
S
UnIT
°C
°F
K
OHM
E
Save value
M
S
M
HI
M
E
6
PASS
S
S
M
S
Lo
M
E
Process value
Software
S
SOF
S
M
version
OPHr
S
E
M
S
E
M
>3 s
E
rES
S
Current value
FACT
rEBO
APPL
HIGH
M
M
S
M
Display menu
4
E
>3 s
S
Current value
S
M
M
DISr
180°
E
Save value
M
M
S
S
>3 s
E
S
Current value
M
DISU
50
200
600
OFF
E
Save value
M
M
S
S
E
>3 s
Current value
S
M
COLr
GrEn
...
r-CW
E
Save value
M
M
S
S
E
>3 s
Current value
S
M
OFF on
DUA
E
Save value
M
M
S
CSP1
M
S
S
CSP2
Selecting PASS step by step
6
Current PASS
S
Gradually upwards (hex.)
>3 s
Pos. 1
0
S
...
S
F
S
fl ashes
S
M
Pos. 2
0
S
...
S
F
S
fl ashes
S
M
M
Pos. 3
S
S
S
0
...
F
fl ashes
S
M
Pos. 4
0
S
...
S
F
S
fl ashes
S
E
Save new
PASS