8. Connecting with M-NET system
■ Connecting the SYSTEM CONTROL Interface to M-NET cable
The room air conditioner can be managed centralized or individually by the system controller using M-NET communications control.
Indoor unit
● To connect with the system controller and ME remote controller, connect the M-NET communication cable
TB520. (It is unpolarized.) Connect 2 core communication cable with A1/B1 or A2/B2. (There will be no problems with connecting to either one.)
● Cross the shield portion of each connecting cable using the S terminal only when cross wiring the communication cables
● After wiring is complete, mount securely with any of mounting cord clamp
When the communication
cable
cross-wired
S
Shield
Communication cable
(M-NET cable)
When the communication
cable
➐
Screw for mounting
Cable tie
* To prevent penetration by condensation, insects, etc., seal the opening well with putty.
Notes
• Electrical work should be performed in accordance with the Technical Standards Regarding Electrical Equipment and the Interior Wiring Standards.
• Connecting wires and remote control cables should be located as far away from other electrical wiring as possible. Placing them too closely
together could cause a malfunction.
• To connect with the M-NET system and MA remote controller, connection is limited to only one unit of the MA remote controller.
• Do not put in the same group as City Multi or P series.
• Test run cannot be conducted from the ME remote controller or the system controller.
■ Setting when M-NET is connected
SW No.
M-NET address
10s position 1s position
SW510
0
SW501
SW510
Refrigerant address
SW580
6
S
B2 A2 B1 A1
TB520
TB521
SW580
0
SW501 SW510
0
0
➊
Interface unit
A1 B1 A2 B2
Communication cable
Communication cable
(M-NET cable)
is not cross wired
Screw for mounting
➑
Cable tie
Mounting cord
➑
➏
clamp (Large)
➎
or (Medium)
Cut with nippers at the notches. Make sure the cut surface is free
of any burr so that the connecting cable does not get damaged.
Address
SW510 sets the 10s position of the address and SW501 sets the 1s position of the address. (Address
setting can be set from 01 ~ 50.)
For example, to set a unit to the address 25, set SW510 to "2" and SW501 to "5."
* The figure to the left is for address 1.
SW501
When the MA remote controller is not used, set the refrigerant address (SW580) to "1."
SW580
B
A
Power supply unit
CN560
➍
➏
to
, and fix with cable tie
When the communication cable
wired and ME remote controller is used
A1 B1 A2 B2
S
Shield
(M-NET cable)
ME remote controller
When the communication
cable
are cross wired
➐
Mounting cord clamp
➏
(Large)
or (Medium)
Screw for mounting
Cable tie
Comments
S
B
A
S
System controller,
etc.
or ME remote control cable
➑
as shown in the figure.
are cross
Note
When cross-wired by the
same terminal box, a 1.25 mm
[AWG 16] line is used.
ME remote controller cable
➎
➐
Screw for
➑
➐
mounting
➑
Cable tie
with
.
2
Mounting cord
➏
clamp (Large)
➎
or (Medium)