t
= 0 - +55°C, -32 - +131°F
amb
115 V a.c. 50/60 Hz
2.5 VA
10 V < U < 256 V
CE (250 V a.c.)
DO1. Refrigeration *
DO2. Defrost *
DO3. Fan or
refrigeration 2 *
DO4. Alarm, light, rail heat
or hotgas defrost *
* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be kept.
** Gold plating ensures make function with small contact loads
*** UL-approval based on 30000 couplings
Koordineret afrimning
Coordinated defrost
RI8MF153
08-2010
INSTRUCTIONS
AK-CC 250 - 115 V
UL *** (240 V a.c.)
10 A Resistive
10 (6) A
5FLA, 30LRA
10 A Resistive
10 (6) A
5FLA, 30LRA
6 A Resistive
6 (3) A
3FLA, 18LRA
131 VA Pilot duty
4 (1) A
4 A Resistive
Min. 100 mA**
131 VA Pilot duty
Type: Pt 1000 (1000 Ω /0°C ) /
Data communication MOD-BUS:
Ptc 1000 (1000 Ω /25°C ) /
NTC-M2020 (5000 Ω / 25°C)
( o06)
No
Function

Publicidad

loading

Resumen de contenidos para Danfoss AK-CC 250

  • Página 1 INSTRUCTIONS AK-CC 250 - 115 V = 0 - +55°C, -32 - +131°F 115 V a.c. 50/60 Hz 2.5 VA 10 V < U < 256 V Type: Pt 1000 (1000 Ω /0°C ) / Ptc 1000 (1000 Ω /25°C ) / CE (250 V a.c.)
  • Página 2 — Elforbindelser - Electrical connections - Elektrische Verbindungen ! ! ! l = max. 15 m *) DI1, DI2: AU: Guld, Gold, Or, Oro Instructions RI8MF153 © Danfoss 08/2010 AK-CC 250 - 115 V...
  • Página 3 Delay of hot gas injection 0 min 60 min 0 min Fan stop at cutout compressor Delay of fan stop 0 min 30 min 0 min Fan stop temperature (S5) -50.0°C 50.0°C 50.0°C AK-CC 250 - 115 V Instructions RI8MF153 © Danfoss 08/2010...
  • Página 4 **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited Factory settings are indicated for standard units. Other code numbers have custom- ized settings. Instructions RI8MF153 © Danfoss 08/2010 AK-CC 250 - 115 V...
  • Página 5 S 32 Delay of output at start-up Heat function r36 is active The defrost temperature cannot be dis- played. There is stop based on time Defrost in progress Password required AK-CC 250 - 115 V Instructions RI8MF153 © Danfoss 08/2010...
  • Página 6 Delay of hot gas injection 0 min 60 min 0 min Fan stop at cutout compressor Delay of fan stop 0 min 30 min 0 min Fan stop temperature (S5) -58.0°F 122.0°F 122.0°F Instructions RI8MF153 © Danfoss 08/2010 AK-CC 250 - 115 V...
  • Página 7 **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited Factory settings are indicated for standard units. Other code numbers have customized set- tings. AK-CC 250 - 115 V Instructions RI8MF153 © Danfoss 08/2010...
  • Página 8 S 32 Delay of output at start-up Heat function r36 is active The defrost temperature cannot be dis- played. There is stop based on time Defrost in progress Password required Instructions RI8MF153 © Danfoss 08/2010 AK-CC 250 - 115 V...
  • Página 9 60 min 0 min Ventilateur Arrêt du ventilateur à compresseur déclenché Temporisation de l’arrêt du ventilateur 0 min 30 min 0 min Arrêt de ventilateur température (S5) -50.0°C 50.0°C 50.0°C AK-CC 250 - 115 V Instructions RI8MF153 © Danfoss 08/2010...
  • Página 10 Le réglage départ usine spécifié s’applique aux appareils standards. Un ***) Le code d’accès 2 permet de limiter les accès à ces menus autre numéro de code indique un réglage départ usine modifié en accord avec le client. Instructions RI8MF153 © Danfoss 08/2010 AK-CC 250 - 115 V...
  • Página 11 Refroidissement forcé S 32 Temporisation des sorties à la mise en route Fonction chauffe r36 active Température de dégivrage pas accessible Arrêt sur temps Dégivrage en cours Mot de passe imposé AK-CC 250 - 115 V Instructions RI8MF153 © Danfoss 08/2010...
  • Página 12 48 hours 0 hours erando Desescarche bajo demanda: variación permitida a S5 0.0 K 20.0 k 20.0 K Retardo de desescarche por gas caliente 0 min 60 min 0 min Instructions RI8MF153 © Danfoss 08/2010 AK-CC 250 - 115 V...
  • Página 13 Temperatura de corte (set point) Estado de la entrada DI2 (OFF=contacto abierto/ ON=contacto cerrado) Temperatura medida con la "sonda de display" (S4%) Temperatura medida con la "sonda de alarma" (S4%) AK-CC 250 - 115 V Instructions RI8MF153 © Danfoss 08/2010...
  • Página 14 ** Estado del relé para compresor 2 *) Sólo pueden ajustarse si el AK está parado (r12=0) **) Pueden operarse manualmente si r12=-1 ***) Con código de acceso 2, el acceso a estos menús será limitado. Instructions RI8MF153 © Danfoss 08/2010 AK-CC 250 - 115 V...
  • Página 15 Se está realizando un desescarche PS: introduzca contraseña (Código de acceso) The Product contains electrical components AK-CC 250 - 115 V Instructions RI8MF153 © Danfoss 08/2010 And may not be disposed together with domestic waste. Equipment must be separate collected with Electrical and Elec-...
  • Página 16 Instructions RI8MF153 © Danfoss 08/2010 AK-CC 250 - 115 V...