Descargar Imprimir esta página

Jung eNet FM J 50700 UP Instrucciones De Servicio página 8

Publicidad

Idiomas disponibles

Idiomas disponibles

eNet
Actuador vía radio persianas
Priority, wind alarm
Priority, sun protection
Priority, twilight
Slat change­over time
Fabric­stretching time
Moving time
Minimum change­over­time
Invert movement direction
Operating hours up
Operating hours down
82581423
J:0082581423
0...4
Basic setting: 3
0...4
Basic setting: 0
0...4
Basic setting: 0
0 ms ... 10 sec
300 ms ... 10 s
Basic setting: 0 ms / 300 ms
1 ... 600 sec
Basic setting: 120 s
300 ms ... 10 sec
Basic setting: 1 s
On, Off
Basic setting: Off
0...65535
Basic setting: Current value
0...65535
Basic setting: Current value
8/9
Specifies the priority for reca­
lling and removing a scene of
type Wind alarm for the chan­
nel.
Specifies the priority for reca­
lling and removing a scene of
type Sun protection for the
channel.
Specifies the priority for reca­
lling and removing a scene of
type Twilight for the channel.
Absolute time for changing­
over Venetian blind slats. The
fabric stretching time can also
be set here for the Awning
operating mode.
Absolute time which the
blind/shutter requires from the
top to the bottom end position.
The entry is essential if scene
or position movements are to
occur.
Minimum interruption time
when changing directions. In­
creasing the minimum chan­
ge­over time will cause less
wear on the motors.
Inverts the activation of the re­
lay outputs. During inverted
operation, the relay outputs
"Up" and "Down" should be
activated in reverse. This is re­
quired, for example, for con­
trolling skylights.
The time is counted during
which the load is physically
switched on (relay contact clo­
sed).
This parameter can be reset to
"0", for example after exchan­
ging the load.
The Reset button is used to
reset the counter to "0". The
device must be programmed
to apply the change.
The time is counted during
which the load is physically
switched on (relay contact clo­
sed).
This parameter can be reset to
"0", for example after exchan­
ging the load.
The Reset button is used to
reset the counter to "0". The
device must be programmed
to apply the change.
13.03.2014

Publicidad

loading