2.2 Pipe connection
Please ensure that all local rules and regulations are complied with, including CE marking of the flue pipe.
Additionally, distance requirements to flammable material for the pipe must be respected.
A flue pipe with an internal diameter of 150 mm should be used for all Aduro stoves.
Aduro 14, 15.2 & 19
Aduro 15, 15.3 & 21
2.3 Connection to a brick chimney
If the stove is being connected to a brick chimney you should use the rear outlet (this does not apply to
Aduro 14, 15.2 & 19) or a curved flue pipe via the top outlet. After measuring, a hole is made in the chimney
in which the pipe sleeve is placed, and stove mortar is used to seal it in place. The stove is placed in position
and the flue pipe is put in place. A thin gasket is placed between the flue pipe and the pipe sleeve to seal the
joints The flue pipe should protrude into the pipe sleeve but must not block the opening in the chimney (see
the illustration below). You may benefit from putting a slim gasket between the flue on the stove and the flue
pipe.
The stove can be connected to a chimney to which other heat sources are connected.
Applies to Aduro 15.3:
Aduro 15.3 must be mounted onto brick chimneys including insulated chimney elements. The stove cannot
be mounted directly to a brick chimney without insulated chimney elements or directly onto insulated
chimney elements as shown below:
The stove leaves the factory with the flue outlet mounted on the top.
The stove leaves the factory with the flue outlet mounted on the top. If you
require the flue outlet on the back, "break" off the cover plates positioned at
the top of the back of the stove. Exchange the exhaust connector (from the
top outlet) with the cover plate from the rear outlet. Mount the cover plate
from the rear outlet to the top outlet. The top outlet is finished with the plate
that lies in the ashpan. You may benefit from putting a slim gasket between
the flue on the stove and the flue pipe.
30