OPERATION / FUNCTION DISPLAY
5.1 Operation of the water detector SHT 5001
LED POWER is green: The SHT 5001 water detector is connected to the mains supply and
mains voltage.
LED SENSORS lights up: As soon as the sensor recognizes a rising water level, its LED will
blink red. The alarm is set off and the potential-free relay 1 and 2 switches.
The acoustic alarm (Relay 2) is deactivated by pressing the button <RESET> once.
Alarm message with storage function: The alarm stays and the relay 1 is switched on,
until the message is removed by pushing the <RESET> button.
Alarm message without storage function: The alarm remains and the relay 1 is switched
on, until the sensor no longer reports water.

5.2 Function test

5.2.1 Function test SHT 5001
By pushing the <TEST> button, the alarm LEDs of the sensor m ust blink red, and the relay
must switch. The pushing of the <RESET> button ends the function test.
5.2.2 Funktionstest SHT 5006
Touch both sensor contacts with a waterlogged cloth or an electric conductive metal and the
alarm is set off immediately.
For your own safety, we recommend that you carry out this test constantly!
6.

TECHNICAL SPECIFICATIONS

Operating voltage:
Power consumption:
Sensor connection:
Cable length of sensor:
Relay contact:
Switching capacity relay:
Operating temperature:
Protection type:
Dimensions (HxWxD):
12
230 V AC (+/-10%) / 50-60 Hz
approx. 3 W
5 (parallel)
up to 50 m (max.)
2 potential-free two-way contacts
max. 5 A / 230 V
0 °C / +40 °C
IP 20
57x72x90 mm