3. Installation
3.1
Installation location
Make sure that the cabinet is installed in a non-
combustible environment or leave a safe distance
from combustible objects (we recommend at least
10 cm). This distance must be verified in conjunc-
tion with a risk assessment.
Important!
The cabinet may only be installed inside a
building.
Do not install it in living areas.
Do not install it near emergency escape routes.
Fire risk. For safety reasons, the top of the
cabinet should be kept clear.
Do not place any kind of hazardous materials
in the vicinity of the cabinet (for example spray
cans, flammable liquids etc.).
In order to ensure proper installation, the cabi-
net must be installed directly on the floor.
The following applies to operation without
ventilation:
Select a ground-level installation location within
the building that allows for rapid evacuation of
the cabinet in the event of damage.
►Tip: The optional set of castors (order no.
11657) can considerably facilitate the evacua-
tion process.
The cabinet's evacuation route should be
marked as a restricted area so that the cabinet
can be moved outside quickly in the event of a
fire.
The installation location should be in a well-
ventilated room. Consider the amount of smoke
in the event of a fire.
It is generally recommended to connect the cabinet
to a ventilation pipe so that fumes and pressure
surges can be discharged to the outside in the
event of a battery fire.
GB