2/4
Motor Protection Circuit Breaker
1)
1)
Wiring Diagrams for 1- or 2-Phase Application
For 1- or 2-Phase Motor Application
2)
Set to 105% of motor current.
Stellen Sie 105% des Motorstromes ein.
Régler à 105% de la valeur du courant moteur.
Regolare a 105% della corrente del motore
Ajustar a 105% de la corriente del motor.
Publication 140MT-IN018A-MU-P - October 2021
-WTEN
1. Prepare wires according to the instructions
2. Open terminal screws completely
3. Insert wires fully in the correct position
4. Tighten terminal screws with the required torque
5. Check for solid connection by pulling on all the wires
Voltage (V)
X1, X2 mm
400
500
690
Frame type
140MT -C*
140MT -D*
WARNING: Do not set outside scale !
WARNUNG: Nicht ausserhalb Skala einstellen !
AVERTISSEMENT: Défense d'ajuster le courant
en dehors de la plage indiquée !
AVVERTENZA: E vietato di regolare la corrente fuori
dal campo di taratura !
ADVERTENCIA: !Prohibido de regular la corriente fuera
del campo de la escala !
ПРЕДУПРЕЖДЕНИЕ: Выставлять уставку в
пределах диапазона!
PN- 650007 DIR 10006443768 (Version 00)
Steps for
a proper
connection
inch
Y mm inch
30
1-3/16
9
23/64
30
1-3/16
9
23/64
50
1-31/32
30
1-3/16
Z mm
inch
7,5
19/64
13,5
17/32