Descargar Imprimir esta página

Ferroli BLUEHELIX TECH RRT 24 H Instrucciones De Uso, Instalación Y Mantenimiento página 173

Ocultar thumbs Ver también para BLUEHELIX TECH RRT 24 H:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

BLUEHELIX TECH RRT 24 H
Use of Ø50 and Ø60 flexible pipe (for ducting only)
The chart includes the starting accessories code 041087X0 for Ø50 and code 041050X0 for Ø60.
Up to 4 m. of Ø80 mm flue can be used between the boiler and the passage with reduced width (Ø50 or Ø60), and up
to 4 m. of Ø80 mm flue on the intake (with max. length of Ø50 and Ø60 flues).
max 4 m
Ø80
To use this width, follow the instructions below.
Access the SC menu (follow the instructions given in par. ""Sc" - Combustion Control Parameters Menu" on page 185)
and bring the parameter SC04 to a value corresponding to the length of the flue used.
SC04
13
12
10
8
6
4
2
0
0
EN
max 4 m
Ø80
fig. 26
10
20
30
fig. 27- Chart for flue parameter choice
cod. 3541C662 - Rev. 00 - 09/2020
A =
Ø50 - 22 m MAX
Ø60 - 60 m MAX
40
50
60
m
70
80
173

Publicidad

loading