Descargar Imprimir esta página

Ametek Powervar Security II Serie Manual Del Usuario página 46

Publicidad

International Models ABCE1102-22 and ABCE1102-22MED
Type
Power Rating (VA/Watts)
Inverter Waveform
Transfer Time
Frequency
BTU/Hr.
T.H.D. w/100% Resistive Load
Online Efficiency (w/o Charger)
Input Voltage
Input Current
Output Voltage
Output Current (VA/Watts)
Input Voltage Range
(w/o Using Battery)
Output Regulation (Mains)
Output Regulation (On Battery)
Backup Time at Full Load (0.7 P.F.)
Floor Mountable
Communications Interface
Shipping Weight (kg)
46
ABCE1102-22
51110-03R
Standard
1100 / 990
Low Distortion Sine Wave
4 ms. Typical
50 / 60 Hz.
239
<4% on Battery
93%
230
8.10 Amps
230
4.80 / 4.30 Amps
185 to 276 volts
± 10%
± 5%
> 5 Minutes
Yes (Optional)
DB9, USB (SNMP Optional)
32
ABCE1102-22MED
51110-23R
Medical Grade
1100 / 990
Low Distortion Sine Wave
4 ms. Typical
50 / 60 Hz.
239
<4% on Battery
93%
230
8.10 Amps
230
4.80 / 4.30 Amps
185 to 276 volts
± 10%
± 5%
> 5 Minutes
Yes (Optional)
DB9, USB (SNMP Optional)
32
A01-00055 Rev P

Publicidad