Power the system on. Use the thermostat to start a cooling or heating cycle,
testing the ERM.
1. Restore power to the compressor/boiler as well as your RedLINK
system.
2. Raise/lower the set point on the zone thermostat to initiate a
call for heat/cooling.
3. Observe all control devices to ensure operation and heat/cool-
ing is active.
4. Lower/raise the set point on the thermostat to suspend the call
for heat/cooling.
5. If outdoor temperature sensor is used, check thermostat to see
the readings are active and accurate.
6. Be sure to set thermostat to the desired settings when checkout
is complete.