Instruction Leaflet IL003036EN
Livret d'instructions IL003036EN
Manual de Instrucciones IL003036EN
BR (1-inch), CH (3/4-inch), and QB (1-inch bolt-on)
GFCI (5 mA), equipment protection (30 mA)
BR (1 po), CH (3/4 po) et QB (1 po boulonné)
DDFT (5 mA), protection de l'équipement (30 mA)
BR (1 pulgada), CH (3/4 de pulgada) y QB (1 pulgada, atornillado)
GFCI (5 mA), protección de equipos (30 mA)
DANGER
FAILURE TO FOLLOW THESE INSTRUCTIONS
COULD RESULT IN DEATH, PERSONAL INJURY, OR
PROPERTY DAMAGE. CIRCUIT BREAKERS MUST
BE INSTALLED AND SERVICED BY A QUALIFIED
ELECTRICIAN. TURN OFF POWER AT THE MAIN
BREAKER BEFORE STARTING INSTALLATION OR
MAINTENANCE.
CAUTION
GFCI BREAKER IS INTENDED FOR
USE WITH:
120/240 VAC SINGLE-PHASE, 60 HZ,
THREE-WIRE SYSTEM
208Y/120 VAC THREE-PHASE, 60 HZ,
FOUR-WIRE SYSTEM
TWO-POLE GFCI CAN BE USED TO PROTECT
240 VAC TWO-WIRE CIRCUITS WITH NO "LOAD
NEUTRAL" WIRE.
ELECTRIC RANGES AND CLOTHES DRYERS WITH
FRAMES GROUNDED BY CONNECTION TO THE
GROUNDED CONDUCTOR, AS PERMITTED BY
THE NEC
, WILL TRIP THE GFCI ON A GROUNDED
®
NEUTRAL CONDITION.
DO NOT CONNECT THE GFCI TO SWIMMING
POOL CIRCUITS INSTALLED PRIOR TO 1965 NEC
REGULATIONS.
DO NOT REVERSE FEED OR BACKWIRE THIS GFCI.
OBSERVE PROPER TERMINATIONS ON THIS GFCI.
DO NOT SUBJECT THIS GFCI TO MEGGER, HIGH
VOLTAGE, OR HI-POT TESTS (REFERENCE SEC.
550-12, 1999 NEC).
Effective September 2023
En vigueur : septembre 2023
Vigencia a partir de septiembre de 2023
DANGER
SI CES INSTRUCTIONS NE SONT PAS SUIVIES
ATTENTIVEMENT, DES BLESSURES CORPORELLES,
VOIRE LA MORT, OU DES DOMMAGES MATÉRIELS
PEUVENT SURVENIR. CONFIER L'INSTALLATION
ET L'ENTRETIEN DES DISJONCTEURS À UN
ÉLECTRICIEN QUALIFIÉ. COUPER L'ALIMENTATION
AU NIVEAU DU DISJONCTEUR PRINCIPAL
AVANT DE COMMENCER L'INSTALLATION OU
L'ENTRETIEN.
MISE EN GARDE
LE DISJONCTEUR DIFFÉRENTIEL DE FUITE À LA
TERRE (DDFT) EST CONÇU POUR ÊTRE UTILISÉ
AVEC :
SYSTÈME À TROIS FILS 120/240 VCA
MONOPHASÉ, 60 HZ
SYSTÈME À QUATRE FILS 208Y/120 VCA
TRIPHASÉ, 60 HZ
UN DDFT BIPOLAIRE PEUT ÊTRE UTILISÉ POUR
PROTÉGER LES CIRCUITS À DEUX FILS DE 240 VCA
SANS FIL DE « CHARGE NEUTRE ».
LES CUISINIÈRES ÉLECTRIQUES ET LES
SÉCHEUSES AVEC DES BÂTIS MIS À LA TERRE
BRANCHÉES AU CONDUCTEUR MIS À LA TERRE,
COMME PERMIS PAR LE NEC
, DÉCLENCHERONT
®
LE DDFT EN CONDITION DE NEUTRE MIS À LA
TERRE.
NE PAS BRANCHER LE DDFT AUX CIRCUITS
DE PISCINE INSTALLÉS AVANT LES
RÉGLEMENTATIONS DU NEC DE 1965.
CE DDFT NE CONVIENT NI À L'ALIMENTATION
INVERSÉE NI AU RACCORDEMENT PAR L'ARRIÈRE.
RESPECTER LES TERMINAISONS APPROPRIÉES
DE CE DDFT.
NE PAS SOUMETTRE CE DDFT À DES ESSAIS DE
MÉGOHMMÈTRE, DE TENSION ÉLEVÉE, NI À DES
ESSAIS DIÉLECTRIQUES (RÉFÉRENCE SEC. 550-12,
1999 NEC).
PELIGRO
EL INCUMPLIMIENTO DE ESTAS INSTRUCCIONES
PUEDE PROVOCAR LA MUERTE, LESIONES
PERSONALES O DAÑOS MATERIALES. LA
INSTALACIÓN Y EL MANTENIMIENTO DE LOS
INTERRUPTORES DEBEN SER REALIZADOS POR
UN ELECTRICISTA CALIFICADO. DESCONECTE LA
ALIMENTACIÓN EN EL INTERRUPTOR PRINCIPAL
ANTES DE INICIAR LA INSTALACIÓN O EL
MANTENIMIENTO.
PRECAUCIÓN
EL INTERRUPTOR GFCI ESTÁ DISEÑADO PARA
USARSE CON:
SISTEMA MONOFÁSICO A TRES
HILOS DE 120/240 V CA, 60 HZ,
SISTEMA TRIFÁSICO A CUATRO
HILOS DE 208Y/120 V CA
PUEDE USARSE UN INTERRUPTOR GFCI BIPOLAR
PARA PROTEGER CIRCUITOS CON DOS HILOS DE
240 V CA QUE NO TENGAN HILO DE NEUTRO EN
EL LADO DE CARGA.
LOS HORNOS ELÉCTRICOS Y LAS SECADORAS
DE ROPA CON CHASIS ATERRIZADO POR EL
CONDUCTOR DE TIERRA, SEGÚN LO PERMITA
EL CÓDIGO ELÉCTRICO NACIONAL (NEC
ESTADOS UNIDOS, NO DEBEN CONECTARSE AL
CIRCUITO DE CARGA DE ESTE INTERRUPTOR GFCI.
NO CONECTE EL INTERRUPTOR GFCI A CIRCUITOS
DE PISCINA INSTALADOS ANTES DE LAS
NORMAS DEL NEC DE 1965.
NO RETROALIMENTE NI CONECTE POR EL LADO
OPUESTO ESTE INTERRUPTOR GFCI.
OBSERVE LAS TERMINACIONES ADECUADAS
EN ESTE GFCI.
NO SOMETA ESTE GFCI A PRUEBAS DE
MEGÓHMETRO, ALTO VOLTAJE O ALTA TENSIÓN
(CONSULTE LA SECCIÓN 550-12, 1999 NEC).