Atlantic NAVIPASS Modbus Manual página 100

Publicidad

NAVIPASS Modbus - Accessory
Configure the "reduced" ambient temperature
on NAVISTEM Bxxxx or RVS63
Heating circuit 1
on the NAVIPASS Modbus
Heating circuit 1
If necessary, modify the incline of the water heating curve
on NAVISTEM Bxxxx or RVS63
Heating circuit 1
on the NAVIPASS Modbus
Heating circuit 1
Case no. 1: Use of the programming schedule set on the boiler
on NAVISTEM Bxxxx or RVS63
Heating circuit 1
on the NAVIPASS Modbus
Heating circuit 1
Case no. 2: Use of the programming schedule set on the customer PLC
Depending on the schedule of your PLC, set the mode changes for the corresponding
heating circuit:
721, 722, 723 CC1, 2.3 (P) operating mode
Note: the following optimization functions are not available in comfort or permanent reduced
mode:
100 / 202
parameter 712
modbus address 136 (0x88)
parameter 720
modbus address 131 (0x83)
parameters 500 to 516.
modbus address 300 (0x12C)
1 : permanent confort
2 : permanently reduced
3 : frost protection
- holiday program
- summer/winter consumption
- daily heating limit
values
-- in °C
-- (0x--) in °C
1 to 40
from 1 to 40 (0x01 to 0x28)
refer to the leaflet of the
NAVISTEM Bxxxx
see page 11 of this leaflet
00ANO0019-G_EN