TRANSPORTATION AND
HANDLING
3. TRANSPORTATION AND HANDLING
Transport the product as close to the installation location as
practical before unpacking
WARNING:
- Do not put any foreign material into the CH Unit and check
to ensure that none exists in the outdoor unit before the
installation and test run. Otherwise, a fire or failure, etc.
may occur.
CAUTION:
- Do not put any material on the product.
- Be careful not to damage on insulation materials of unit's
surface when lifting.
3.1. COmBINATION CH UNIT AND INDOOR UNIT
The CH Unit is Installed indoors for the SET-FREE FSXN
system, between the outdoor unit and Indoor unit. The
combination of the CH Unit and indoor Unit is as follows.
model
Indoor Unit Quantity
CH-6.0N1
1 to 7
CH-10.0N1
1 to 8
NOTE:
- The excess of the total capacity may cause insufficient
performance and abnormal sound. Be sure to connect
within the allowable total capacity.
- In case that the indoor unit total capacity is 10.0HP for CH-
10.0N1, the performance may decrease approximately 5%
in cooling and 10% in heating.
PMML0204 rev.0-05/2010
Total Indoor
Capacity (HP)
Less than 6.0
6.1~10.0