Descargar Imprimir esta página

Mitsubishi Electric CITY MULTI PEFY-WP50VMS1-E Manual De Instrucciones página 8

Ocultar thumbs Ver también para CITY MULTI PEFY-WP50VMS1-E:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 30
3.3. Set temperature
<Cool, Dry, Heat, and Auto (single set point)>
Fri
Room
Cool
Set temp.
Auto
Mode
Temp.
Fan
F1
F2
F3
F4
<Auto (dual set point) mode>
Fri
26
Room
28
Auto
Auto
2
Mode
Temp.
Fan
F1
F2
F3
F4
Set temperature for cooling
Set temperature for heating
Set temperature range
Operation mode
Cool/Dry
19ºC–30ºC/67ºF–87ºF
Heat
17ºC–28ºC/63ºF–83ºF
Auto
19ºC–28ºC/67ºF–83ºF
(single set point)
Auto
Cool: Same as the set temperature range for Cool
(dual set points)
mode
Heat: Same as the set temperature range for Heat
mode
Fan
Not settable
*1 The settable temperature ranges vary, depending on the indoor unit model.
*2 The set temperature for Auto mode (either single or dual set point(s)) will
appear depending on the indoor unit model.
*3 The same values are used for the set temperature for Cool/Dry mode and the
cooling set temperature for Auto mode (dual set points). Likewise, the same
values are used for the set temperature for Heat mode and the heating set
temperature for Auto mode (dual set points).
*4 The cooling and heating set temperatures can be set under the following
conditions.
- The cooling set temperature is greater than the heating set temperature.
- The difference between the cooling and heating set temperatures is equal or
greater than the minimum temperature difference that varies with the indoor
unit model.
KJ79D490H02
Press the [F2] button to decrease the set
temperature, and press the [F3] button to
increase.
* Refer to the table below for the settable
temperature range for different operation
modes.
* Set temperature cannot be set for the Fan
mode.
* Depending on the Temperature unit setting,
temperatures will decrease or increase by
0.5ºC, 1ºC, 1ºF, or 2ºF increments.
Fri
28.5
Room
Cool
Set temp.
Auto
28.5
Mode
Temp.
Fan
Example display
(Centigrade in 0.5-degree increments)
The current set temperatures will appear.
Press the [F2] or [F3] button to display the
Settings screen.
Set temperature range
*1
*1
*1*2
*2*3*4
3.4. Fan speed
Fri
Room
Cool
Set temp.
Auto
Mode
Temp.
Fan
F1
F2
F3
F4
• The number of available fan speeds depends on the indoor unit model.
[PEFY-WP-VMS1-E series]
(Low)
(Mid)
*1 This setting can be adjusted only with MA remote controller.
• The actual fan speed will differ from the fan speed displayed on the LCD when
one of the following conditions is met.
1. While "STAND BY" or "DEFROST" is displayed
2. When the room temperature is higher than the set temperature during the
heating mode
3. Immediately after the heating operation (during stand by for switching the
operation mode)
4. During the Dry mode
8
Press the [F4] button to go through the fan
speeds in the following order.
Auto
(High)
(Auto)
*1

Publicidad

loading