Using the local command push-button
By default, channels 1 and 2 of the push-button panel act as a local actuator command.
The 2 local command push-buttons are used to locally command the roller shutter or the Venetian
blind as follows:
• Pressing down (> 0.5 s) the push-button moves the roller shutter or Venetian blind UP (push-
button 1) or DOWN (push-button 2) for an amount of time equal to the Movement time.
• If the roller shutter or Venetian blind is moving, pressing one of the two push-buttons (≤ 0.5 s)
will stop it.
• In the Venetian blind mode, with the Venetian blind stopped, each time the push-buttons are
pushed briefly (≤ 0.5 s) causes the slats to be inclined.
Even if only one of the two channels of the push-button panel (channel 1 or channel 2) is associated
with a function via the Easy configurator, the local actuator command function is disabled for both
channels.
Adjusting the travel and movement times
To manage the intermediate positions of the roller shutter and the cut off of the motor power supply,
the actuator uses two parameterisable times:
• Travel time, this is the time required for the roller shutter to close completely starting from a
fully open position;
• Movement time, equal to 110% of the travel time, this is the amount of safety time that will
pass before the power supply of the electric motor is cut off.
The following procedure is used to store the travel time in the actuator:
1. Bring the roller shutter to the completely open position ("all up").
2. Press the push-buttons related to channels 3 and 6 at the same time: the corresponding green
LEDs will flash at the same time.
3. Within 5 seconds (before the LEDs stop flashing) press the push-button relative to channel 2
and lower the roller shutter to start counting the travel time.
4. When the roller shutter is completely closed ("all down") press again the push-button related
to channel 2 to stop the travel time and exit the procedure.
To correctly store the travel time, it is recommended to press the push-button immediately
after the roller shutter is completely closed.
IN SERVICE
32