Installation
Do not instal ICAD before welding.
This apply for electrical as well as for
mechanical installation.
Please observe that ICAD when
connected to 24 V d.c., will send out
acoustic noise at stand still. This has no
in uence on the function/operation of
the ICAD.
Use
ICAD 600A, ICAD 600A-TS and ICAD 1200A can
be used together with the following Danfoss
valves ( g. 1, 5a and 5b).
ICAD 600A
ICAD 600A-TS
ICM 20
ICMTS 20
ICM 25
ICM 32
Electrical data
Supply voltage is galvanically isolated from in-/
output.
Supply voltage
24 V d.c., +10% / -15%
Load
ICAD 600A, ICAD 600A-TS: 1.2 A
ICAD 1200A: 2.0 A
Fail safe supply
Min. 19 V d.c.
Load
ICAD 600A, ICAD 600A-TS: 1.2 A
ICAD 1200A: 2.0 A
Anolog Input - Current or Voltage
Current
0/4 - 20 mA
Load: 200 W
Voltage
0/2 - 10 V d.c.
Load: 10 kW
Analog Output
0/4 - 20 mA
Load: ≤ 250 W
Digital Input - Digital ON/OFF input by means of
voltfree contact (Signal/Telecom relays with gold-
plated contacts recommended) – Voltage input
used
ON: Contact impedance < 50 W)
OFF: Contact impedance > 100 kW
Digital Output - 3 pcs. NPN transistor output
External supply:
5 - 24 V d.c. (same supply as
for ICAD can be used, but
please note that the
galvanically isolated system
will then be spoiled).
50 W
Output load:
Load:
Max. 50 mA
Temperature range (ambient)
–30°C/+50°C (–22°F/122°F)
Enclosure
IP 67 (~NEMA 6)
Electrical connection
Connection to ICAD is done via M12 connectors.
ICAD has two M12 male connectors build-in:
Power supply: 4 poled M12 male connector
Control signals: 8 poled M12 male connector
© Danfoss | DCS (MWA) | 2015.12
If ICAD is delivered with cables (1.5 m. (60 in.))
M12 female connectors: (Cable set with M12
female connectors in other lengths are available)
Power Supply cable with 4 poled M12
female connector
3 x 0.34 mm
I:
Black
II: White
III: Brown (–) 24 V d.c.
Control cable with 8 poled M12
female connector
7 x 0.25 mm
A: Black
B: Brown (–) Digital output.
ICAD 1200A
C: Red
ICM 40
D: Orange (–) GND - Ground.
ICM 50
E: Yellow (+) Analog input
ICM 65
ICM 100
F: Green
ICM 125
ICM 150
G: Blue
*) If Neutral zone / 3 point control is
selected (parameter i02 = 3) then
E and G is used as DI2 - Digital
ON/OFF input. Se g. 9.
Electrical installation
General procedure for ICAD 600A/ICAD
600A-TS/1200A installed on all ICM valves.
All necessary electrical connections to be made.
Analog or digital operation of ICM valve.
Fig. 6
Analog operation - 7 wired cable (A-G)
Modulation control. ICM valve to be
controlled from Danfoss electronics, type
EKC/EKE ( g. 7), or third party electronics
(like e.g. PLC).
Connect analog input signals. Currrent
(mA) or Voltage (V). See Parameter list for
con guration of analog input signals.
Yellow (+) and Orange (GND) are used for
current (mA) input.
or
Green (+) and Orange (GND) are used for
Voltage (V) input.
Blue (+) and Orange (GND) are used
for current (mA) output (optional, not
mandatory).
Fig. 6
Digital operation - 7 wired cable (A-G)
ON/OFF ICM solenoid valve operation. ICM
valve to be controlled by means of a digital
voltfree contact.
Connect digital input signals ( g. 8). See
Parameter list for con guration of digital
input signals.
Green (+) and Orange (GND) are connected
to a voltfree contact.
Digital output signals are optional, not
mandatory.
Black (–) and Orange (GND) are connected
to auxiliary relay for Common Alarm.
Brown (–) and Orange (GND) are connected
to an auxiliary relay indicating ICM fully
open.
Red (–) and Orange (GND) are connected
to an auxiliary relay indicating ICM fully
closed.
2
(3 x ~22 AWG) ( g. 6)
(+) 19 - 24 V d.c. fail safe
supply (optional).
(+) 24 V d.c.
2
(7 x ~24 AWG) ( g. 7)
(–) Digital output.
Common Alarm.
ICM fully open.
(–) Digital output.
ICM fully closed.
0/4-20 mA. *)
(+) Analog input 0/2-10 V /
DI1 - Digital ON/OFF
input.
(+) Analog output
0/4-20 mA. *)
Supply voltage - 3 wired cable (I, II, III)
ICAD must be connected to a normal
24 V d.c. supply. As an option, a fail safe
supply is possible by means of a battery or
UPS (Uninterruptible Power Supply). When
voltage is applied as described below, ICAD is
ready to be con gurated. See Parameter list.
ICAD con guration can be done
independently whether the ICAD is installed
on the ICM valve or not.
See Mechanical installation.
Connect the White (+) and Brown (–) to a 24
V d.c. supply voltage ( g. 6).
Fail safe supply as an option (not mandatory).
Connect the Black (+) and Brown (–) to a fail
safe supply.
Mechanical installation
General procedure for ICAD 600A/ICAD
600A-TS/1200A installed on all ICM valves ( g. 3).
Check that the three socket set screws are
fully unscrewed counter clockwise with a 2.5
mm Hexagon key.
Mount ICAD by slowly lowering it on top of
the ICM valve.
The magnet coupling will drag the ICM and
ICAD together and in position.
Push ICAD in place.
Fasten ICM and ICAD with the three socket
set screws using a 2.5 mm Hexagon key.
Special moisture seal is damaged if
screws are removed ( g. 3, pos. A)
Neutral zone / 3 point control ( g. 9)
¡02 = 3
When ¡02 = 3 the factory setting of ¡04
(opening) and ¡14 (closing) are both set to 10.
When ¡02 = 3 the speed given by ¡04 (opening)
and ¡14 (closing) are active
¡13 (Inverse operation) is active
¡16 = 1 (Encoder operation enable) is active.
¡13 = 0 (Direct operation)
DI1 = DI2 = OFF
ICAD/ICM maintain current position
DI1 = DI2 = ON
ICAD/ICM maintain current position
DI1 = ON, DI2 = OFF
ICAD increase opening degree
DI1 = OFF, DI2 = ON
ICAD decrease opening degree
¡13 = 1 (Inverse operation)
DI1 = DI2 = OFF
ICAD maintain current position
DI1 = DI2=ON
ICAD maintain current position
DI1 = ON, DI2 = OFF
ICAD decrease opening degree
DI1 = OFF, DI2 = ON
ICAD increase opening degree
DKRCI.PI.HV0.K4.ML | 520H8962 | 3