Parameter list
(continued)
Description
ICAD
parameter
In ON/OFF Mode
¡14
Closing speed
Manual set point
¡15
Encoder operation
¡16
Forced closing when
i17
ICM valve Opening
Degree < 3%
ICM con guration
¡26
Service
Description
ICV Name
OD %
¡50
AI [mA]
¡51
AI [V]
¡52
AO [mA]
¡53
DI
¡54
DO Close
¡55
DO Open
¡56
DO Alarm
¡57
Display mP SW ver.
¡58
Motor mP SW ver.
¡59
Reset to factory setting:
1. Remove the power supply.
2. Activate down arrow and up arrow push buttons
at the same time.
3. Connect the power supply.
4. Release down arrow and up arrow push buttons.
5. When the display on ICAD ( g. 2) is alternating
between showing: CA and A1 the factory
resetting is complete.
© Danfoss | DCS (MWA) | 2015.12
Min
Max
Factory
Stored Unit
Setting
0
100
50/ 100
0
100
0
0
1
1
0
1
0
0
9
0
Min
Max
Factory
Stored
Setting
0
100
-
0
100
-
0
100
-
0
100
-
0
1
-
0
1
-
0
1
-
0
1
-
0
100
-
0
100
-
Pass
Comments
word
-
No
See ¡04.
If ¡26= 1 - 3 then factory settin qg = 100
If ¡26= 4 - 9 then factory setting = 50
No
When ¡01= 2, ¡15 determine the start up value.
Yes
NB: Password protected. Password = 7
0: Encoder disabled. Means ICAD operation as ICAD 600A/ICAD 600A-TS/1200A
without encoder
1: Encoder enabled
-
No
Enable/Disable forced closing
0: When ICM valve Opening Degree < 3% it will be forced to close regardless of
requested ICM valve Opening Degree
1: When ICM valve Opening Degree < 3% no forced to closing will take place
Yes
NB: Password protected. Password = 11
0: No valve selected. Alarm A1 will become active.
1: ICM 20 with ICAD 600A / ICMTS 20 with ICAD 600A-TS
2: ICM 25 with ICAD 600A
3: ICM 32 with ICAD 600A
4: ICM 40 with ICAD 1200A
5: ICM 50 with ICAD 1200A
6: ICM 65 with ICAD 1200A
7: ICM 100 with ICAD 1200A
8: ICM 125 with ICAD 1200A
9: ICM 150 with ICAD 1200A
Unit Pass word Comments
%
-
ICM valve Opening Degree
mA
-
AI signal
V
-
AI signal
mA
-
A0 signal
-
-
DI signals. Depending of ¡02
If ¡02 = 2, one digits are shown. See g. 8
0 : DI1 = OFF
1 : DI1 = ON
If ¡02 = 3, two digits are shown. See g. 9
00 : DI1 = OFF, DI2 = OFF
10 : DI1 = ON, DI2 = OFF
01 : DI1 = OFF, DI2 = ON
11 : DI1 = ON, DI2 = ON
-
-
DO Closed status. ON when OD < 3 %
-
-
DO Open status. ON when OD > 97 %
-
-
DO alarm status. ON when a Alarm is detected
-
-
Software version for display microprocessor
-
-
Software version for motor microprocessor
DKRCI.PI.HV0.K4.ML | 520H8962 | 6