When the pipeline pressure is too high, to maintain an adequate flow rate, user can set the running
capacity to 105%~120%. The pump will run at a higher speed but will not exceed the rated power
of each model. If the pump has reached the rated power at 100% and user continues to increase
the running capacity, the display will return to 100% when the motor speed is stabilized.
5.6 Auto-Inverter Mode (Advanced users)
Under Auto Inverter Mode, the pump can automatically detect the system pressure and adjust the speed
of motor to reach the set flow.
1
Unlock the screen, press
Inverter mode.
2
The flow rate could be adjusted, by pressing
3
The unit of flow rate could be changed to LPM, IMP GPM or US GPM, by pressing both
4
Press
Self-learning:
When first switching to the Auto-Inverter mode manually or via external control or activating timer mode
with flow rate setting, the system will perform the self-learning process for 180s and redefine the adjustable
flow range of the pump by detecting the pipeline pressure.
eg: the default adjustable flow range of Moov Ai Pump is 22-110 US GPM, after self-learning, the range
may be redefined to 22-95 US GPM. If the set flow is beyond the current adjustable range, the actual
achievable flow rate will be displayed after the motor speed is stabilized.
for more than 3 seconds to unlock the screen;
to start. The pump will run at 80% of the running capacity after
or
to set the running capacity between 30%~120%, each
again to switch to Auto-Inverter mode.
to switch from the Manual-Inverter mode to Auto-
for 3 seconds
to switch to Manual-Inverter mode
or
with 1m³/h for each step.