TCB-IFDMR01UP-UL
(Terminal block with relay)
MAX. 328'1" (100 m)
DI6
(Input, DC5 V)
DI6
Input
Name
DI6
Operation ON/OFF Input
- Digital Output functions -
The specifications of Terminal DO1 to DO6 are as follows.
TCB-IFDMR01UP-UL
(Terminal block with relay)
MAX. 1640'5" (500 m)
DO1 -
DO6
DO1 - DO6
• Use the contact side of the relay terminal used in TCB-IFDMR01UP-UL according to the specifications shown in the
table below.
Relay model name
G2RV-SR700-12DC
Locally procured
Relay coil signal
When using with DDC, it starts by turning on this terminal.
External trouble Input signal type(pulse / static) is selectable by
Jumper Wire J01 on the Indoor(DX) P.C. board - MCC-1777
• Connect (Default) : Pulse / Cut : Static
Note the unit will not operate until there is an appropriate 0-10 V
Capacity Control signal.
The position of J01 (MCC-1777)
J01
Connect
Cut
Locally procured
11
14
Contact rating
250 V max / 3 A max
(Minimum Current: 10 mA more)
Description
Action
Pulse input
ON
(At factory setting)
Pulse width 200 to 300 ms
Pulse interval 200 to 300 ms or more.
Static input
Load conditions
Resistive load
– 18 –