Toshiba Carrier TCB-IFDMR01UP-UL Manual Del Usuario página 47

Ocultar thumbs Ver también para TCB-IFDMR01UP-UL:

Publicidad

Idiomas disponibles

Idiomas disponibles

Register
address
Input Register
30073 ~ 30078
30079
30080
30081
30082
30083
30084 ~ 30099
30100
30101
30102
30103
30104
30105
30106
30107
30108
30109
30110
30111
30112
30113
30114
30115
30116 ~ 30199
30200
30201
30202
30203
30204
30205
30206
30207
30208 ~ 30249
30250
30251
30252
30253
30254
30255
30256
30257
30258 ~ 30299
30300
30301
30302
Read / Write
R
Reserved
Under restriction of compressor speed due
to heat sink overheating in outdoor unit(s)
Cooling / heating start control output
Defrost Mode Digital Output
Pre defrost signal output
Cooling oil recovery / Heating ref recovery
Reserved
Product type setting
Control type
Operation mode range
Fan speed range
Cooling upper limit set temperature
Cooling lower limit set temperature
Heating upper limit set temperature
Heating lower limit set temperature
Dry upper limit set temperature
Dry lower limit set temperature
Automatic mode upper limit set
temperature
Automatic mode lower limit set
temperature
Dual Set point Function Status
Setting capacity
Modbus band rate SW state
Modbus Slave Address SW state
Reserved
Model name
Model name
Model name
Model name
Model name
Model name
Model name
Model name
Reserved
Serial number
Serial number
Serial number
Serial number
Serial number
Serial number
Serial number
Serial number
Reserved
Firmware Definition
(Firmware control number)
Firmware Definition
(Firmware control number)
Software Version
– 45 –
Data
Byte
0 : OFF
2
1 : ON
0 : OFF
2
1 : ON
0 : OFF
2
1 : ON
0 : OFF
2
1 : ON
0 : OFF
2
1 : ON
2 FIX AT : 0
0 : TA type
2
1 : TF type
2 : DDC type
Bit0 : FAN MODE
Bit1 : COOLING
2
Bit2 : DRY MODE
Bit3 : HEATING
Bit5 : AUTO MODE
Bit1 : FAN [L]
2
Bit2 : FAN [H]
Bit3 : FAN [HH]
2 10 times values
2 10 times values
2 10 times values
2 10 times values
2 10 times values
2 10 times values
2 10 times values
2 10 times values
0 : OFF
2
1 : ON
2 Similar setting to DN[11] setting
0 : 9600bps
1 : 19200bps
2
2 : 38400bps
3 : 57600bps
2 0 ~ 15 (0=slave address 1)
16
16
0×2199
4
0×0001
2
Data Definition and remarks