Descargar Imprimir esta página

Toshiba Carrier TCB-IFDMR01UP-UL Manual Del Usuario página 46

Ocultar thumbs Ver también para TCB-IFDMR01UP-UL:

Publicidad

Idiomas disponibles

Idiomas disponibles

Register
address
Input Register
30001
30002
30003
30004
30005
30006
30007
30008
30009 ~ 30019
30020
30021
30022
30023
30024 ~ 30039
30040
30041
30042
30043
30044
30045
30046
30047 ~ 30059
30060
30061
30062
30063
30064
30065
30066
30067
30068
30069
30070
30071
30072
* There are possibilities of thermodynamic and/or mechanical limitation from many factors. which may affect our system's
heat pump cycle (refrigerant cycle) during operation. Hence, there is a possibility that the capacity output may be different
from capacity control setting.
Read / Write
R
Operation / stop setting
Operation mode setting
Set temperature setting
Automatic cooling set temperature
(Dual set point) setting
Automatic heating set temperature
(Dual set point) setting
Fan speed setting
Operation prohibition setting
Analogue Input Capacity Control*
Reserved
CN90 DI1 (Safety contact input)
CN90 DI2 (External error input)
CN90 DI3 (Forced Thermo OFF input)
CN90 DI4 (Notice input)
Reserved
TC1
TC2
TCJ
TA
TF
Tx (Auxiliary temperature sensor)
TO
Reserved
Alarm Code
Notice code 1
Notice code 2
Notice code 3
Notice code 4
Notice code 5
Thermostat On Digital Output
Cooling operation signal output /
secondary heating signal output
Heating operation signal output
Fan Motor Digital Output
Operating output
Outdoor unit(s) operation level is lower
than capacity command
Outdoor unit(s) operation level is higher
than capacity command
Data
Byte
– 44 –
Data Definition and remarks
0: STOP
2
1: OPERATE
1: HEATING MODE
2
2: COOLING MODE
3: DRY MODE
2 10 times values
2 10 times values
2 10 times values
1 : FAN STOP
2 : FAN AUTO
2
3 : FAN SPEED [HH]
4 : FAN SPEED [H]
5 : FAN SPEED [L]
Bit0 : Operation STOP
Bit1 : Operation Mode
2
Bit2 : temperature setting
Bit4 : FAN
2 0 ~ 15
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON
2 10 times values
2 10 times values
2 10 times values
2 10 times values
2 10 times values
2 10 times values
2 10 times values
For example : remote controller display
2
E04 → 0×0044
For example : remote controller display
2
201 → 129
For example : remote controller display
2
201 → 129
For example : remote controller display
2
201 → 129
For example : remote controller display
2
201 → 129
For example : remote controller display
2
201 → 129
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON
2 0 : OFF
1 : ON

Publicidad

loading

Este manual también es adecuado para:

Rbm-a0601upva-ulRbm-a1201upva-ulRbm-a1921upva-ul