ADJUSTMENT LOGICS:
The thermostat operation (either cooling or
heating) takes place with a difference of 0,2°C
from the set point of the controller (Fig. 6). The
thermostat switches on the fan and opens the
valve (if any).
Ventilation is activated (limited to 2 minutes
every 8 minutes) and forced without a real ne-
cessity only with the following setting: cooling
mode and remote air probe; this is due to the
fact that in this situation a good air temperature
detection is possible only if the air is periodically
moved.
7
TECHNICAL SPECIFICATIONS
Technical specifications
Power supply
No. IP protection rating
Output relays
Temperature probes
Electric class of protection EYTED2T / EYTED4T
Electric class of protection EYTED10
Dimension
The water consent to ventilation (only if the wa-
ter probe is connected) is driven by the activa-
tion and deactivation logic reported in figure
7; in case of EYTED4T and EYTED10 the water
consent to ventilation is active only in heating
mode.
In the EYTED10 version the fan speed can be
setted manually (like EYTED2T and EYTED4T)
or working automatically according to distance
between room temperature and temperature
SET (Fig.8).
230 V - 50/60Hz
IP30
6(2)A/250V
NTC 10K Ohm @25°C
II
I
125 x 75 x 32 mm