Operating Instructions
Safety Relay ESM-BA7..
6. Activating safety function:
Open the emergency stop circuit by actuating the
connected safety switch. The safety contacts open
immediately.
7. Reactivating:
Close the emergency stop circuit. If Automatic
start is selected, the safety contacts will close
immediately.
If the Monitored manual start behavior is set, close
the start button to close the safety contacts.
What to do in case of a fault?
Device does not switch on:
Check the wiring by comparing it to the wiring
f
diagrams.
Check the safety switch used for correct function
f
and adjustment.
Check whether the emergency stop circuit is
f
closed.
Check whether the start button (with manual start)
f
is closed.
Check the operating voltage at A1 and A2.
f
Is the feedback loop closed?
f
Device cannot be switched on again after an
emergency stop:
Check whether the emergency stop circuit was
f
closed again.
Was the start button opened before closing of the
f
emergency stop circuit (with manual start)?
Is the feedback loop closed?
f
If the fault persists, perform the steps listed under
Setup procedure.
If these steps do not remedy the fault either, return
the device to the manufacturer for examination.
Opening the device is impermissible and will
void the warranty.
Maintenance
The device must be checked once per month for
proper function and for signs of tampering and
bypassing of the safety function. The device is
otherwise maintenance-free, provided that it was
installed properly.
Disposal
Pay attention to the applicable national regulations
and laws during disposal.
Declaration of conformity
The EU declaration of conformity can be found at
www.euchner.com. Enter the order number of your
device in the search box. The document is available
under Downloads.
Service
If servicing is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen
Germany
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.com
Technical data
Parameter
Operating voltage
Rated supply frequency
Permissible deviation
Power consumption
Control voltage at S11
Control current S11 ... S14
Safety contacts
Auxiliary contacts
(81-82, 91-92, 101-102, 101-112)
Transistor auxiliary contacts (O1, O2)
Max. switching voltage
Safety contact breaking capacity
(13-14, 23-24, 33-34, 43-44, 53-54,
63-64, 73-74)
Max. cumulative current of all safety
contacts up to T
 = 40 °C
a
Breaking capacity, auxiliary contacts
(81-82, 91-92, 101-102, 101-112)
Minimum contact load
Contact fuses
Conductor cross-section
Tightening torque (min./max.)
Typ. switch-on delay/switch-off delay for
the normally open contacts upon demand
from the safety circuit
Max. length of control line
Contact material
Mech. contact life
Test voltage
Rated impulse withstand voltage, leakage
paths/air gaps
Rated insulation voltage
Degree of protection
Temperature range
Installation altitude
Degree of contamination
Overvoltage category
Weight
Mounting
Characteristics according to EN ISO 13849-1 for all variants of the series ESM-BA7
Load (DC-13; 24 V)
n
op
T
10D
Category
PL
PFH
D
1) Additional data can be requested from the manufacturer for applications that deviate from these conditions.
6
Value
AC/DC 24 V
50 - 60 Hz
± 10%
DC 24 V
Approx. 4.5 W
DC 24 V
Approx. 250 mA
7 NO contacts
4 NC contact
+24 V switching, max. 30 mA, short-circuit-proof
AC 250 V
AC: 250 V, 2,000 VA, 8 A for ohm resistive load (6 operating cycles/min)
250 V, 3 A for AC-15
DC: 40 V, 320 W, 8 A for ohm resistive load (6 operating cycles/min)
24 V, 3 A, for DC-13
35 A (housing distance 10 mm)
20 A (housings closely spaced)
AC: 250 V, 2,000 VA, 8 A
DC: 40 V, 320 W, 8 A
5 V, 10 mA
10 A gG
0.14 - 2.5 mm²
0.5 Nm/0.6 Nm
< 30 ms/< 20 ms
2 x 1000 m with 1.5 mm², 2 x 500 m with 0.75 mm²
AgSnO
2
Approx. 1 x 10
2.5 kV (control voltage/contacts)
4 kV (DIN VDE 0110-1)
250 V
IP20
DC 24 V: -15 °C to +40 °C
≤ 2000 m (above sea level)
2 (DIN VDE 0110-1)
3 (DIN VDE 0110-1)
Approx. 350 g
Mounting rail according to DIN EN 60715 TH35
1)
≤ 0.1 A
≤ 1 A
≤ 500,000 cycles
≤ 350,000 cycles
20 years
4
e
2.47 x 10
-8
AC 24 V
Approx. 8.5 VA
7
≤ 2 A
≤ 100,000 cycles
1/h

Publicidad

loading

Este manual también es adecuado para:

Esm-ba701pEsm-ba701097225097224