WARNINGS AND ALARMS
DPR
COD. ALARM
DESCRIPTION
O
DRY RUNNING
A01
( ( O ) )
O
MINIMUM PRES-
A11
SURE
( ( O ) )
O
A02
OVERLOAD
( ( O ) )
DAMAGED
A05
O
PRESSURE
TRANSMITTER
DRY-RUNNING
A21
((O))
(BY EXTERNAL
LEVEL INPUT)
A30
O
ANTI-FLOODING
EXTERNAL DISA-
EL-
O
BLING
MEMBRANE
MBr
O
REPLACEMENT
---
O
OVER-PRESSURE It will automatically restore operation when the external input enables operation.
EPR
ALARM
DESCRIPTION
O
DRY RUNNING
( ( O ) )
CLASSIFICATION AND TYPE
According to IEC 60730-1 and EN 60730-1 this unit is a control sensor device, electronic, independent assembly, with ac-
tion type 1B (microdisconnection). Operating value: I <20% I learned. Pollution degree 2 (clean environment) or flow>2,5 l/
min. Rated impulse voltage: cat II / 2500V. Temperatures for ball test: enclousure (75) and PCB (125).
When is detected a dry-run operation the pump is automatically stopped. By mean
of ENTER the normal operation can be manually restored.
After the activation of the dry-running alarm if the Automatic system reset (ART) is
enabled, a first attempt at 5 minutes and then an attempt every 30 minutes for 24
hours is performed in order to restore the normal operation. This alarm can also be
reset manually with the ENTER push-button. If the alarm persists after 24 h we find a
definitive alarm.
When is detected a pressure below a pre-set value and for a pre-set period of time
in the ADVANCED PROGRAMMING MENU, the pump is automatically stopped. The
minimum pressure helps to detect a dry-run operation or pumps running far from its
best efficiency point. This alarm is reset automatically as soon as the pressure exceeds
the limit value.
By mean of ENTER the normal operation can be manually restored.
After the activation of the minimum pressure alarm if the Automatic system reset
(ART) is enabled, a first attempt at 5 minutes and then an attempt every 30 minutes
for 24 hours is performed in order to restore the normal operation. This alarm can
also be reset manually with the ENTER push-button. If the alarm persists after 24 h
we find a definitive alarm.
Overload alarm is activated when the nominal pump current is exceeded. 4 automatic
reset attempts prior to the final alarm are performed.
Normal operation can also be restored manually by pressing ENTER.
CONTACT WITH YOUR SUPPLIER
Only if tE1 has been activated in the advanced programming menu.
The alarm is displayed on the screen when the float switch detects a low level of
water in the suction tank, stopping the operation of the pump. It is automatically
restored when there is water again.
FLOOD protection has been activated because the pump has been running conti-
nuously for a period of time equal to the limit set in the ADVANCED MENU.
It is manually reset by pressing ENTER.
Only if tE2 has been enabled in the advanced programming menu.
The alarm is displayed on the screen when the device is disabled by external input
action.
It will automatically restore operation when the external input enables operation.
The alarm is displayed on the screen when the device is disabled by external input
action.
When is detected a dry-run operation the pump is automatically stopped. By mean of EN-
TER the normal operation can be manually restored.
After the activation of the dry-running alarm if the Automatic system reset (ART) is enabled,
a first attempt at 5 minutes and then an attempt every 30 minutes for 24 hours is performed
in order to restore the normal operation. This alarm can also be reset manually with the
ENTER push-button. If the alarm persists after 24 h we find a definitive alarm.
SYSTEM REACTION
SYSTEM REACTION
7