INSTALLATION INSTRUCTIONS
Electric Wiring and Applications Cont.
4. E2 control parameters display and setting
Each need to be set, setting method:
1. Press START (SW5) for 2 seconds. Display will show 1111, enter the set state. Flashing display the current value.
2. Press UP (SW4) or DOWN (SW7) to adjust the parameters.
3. After the adjustment is completed:
<A> In the current state of code, effectively set the time by pressing STOP (SW6) for 2 seconds, showing 0000. Keep
the current settings and exit the set state, stop flashing display, waiting for 2 minutes after the power off and then
power up again.
<B> The cuurent set time is not set by STOP (SW6) or change the dial selection, do not save the current set value, exit
the set state, stop flashing display.
<C> Effective time setting: the machine with the contract number and set off a low temperature automatic operation
function for 10 minutes, the other for 30 seconds.
SW1
SW2
SW3
Function
15 (F)
10 (A)
1
Selection of the maximum allowable outside
circumstance temperature for IDU's electrical heating.
(IDU entering auxiliary electric heating mode based on
the outside temperature selection).
15 (F)
11 (B)
1
The maximum allowable use of the outside circumstance
temperature remove's temperature difference selection
for IDU's electric heating. (IDU exiting auxiliary electric
heating based on the temperature difference selection)
15 (F)
12 (C)
1
ODU heat pump lock outside circumstance temperature
selection. (ODU heat pump entering lockout mode based
on outside temperature selection).
15 (F)
13 (D)
1
ODU heat pump lock --- outside circumstance
temperature remove's temperature difference selection.
(ODU heat pump exiting lockout mode based on the
temperature difference selection)
49-5000878 Rev. 0
Digital tube LD1 ~ 4 Display
0 - No limit
1: Force off the electric heating
2: -20°F
3: -15°F
4: -10°F
5: -5°F
6:
5°F
7: 15°F
8: 25°F
9: 35°F
10: 45°F
11: 55°F
12: 65°F
0: 5°F
1: 10°F
2: 15°F
0 - No Locking Function
1: Forced heat pump shutdown
2: -23°F
3: -20°F
4: -15°F
5: -10°F
6: -5°F
7:
0°F
8:
5°F
9: 10°F
10: 15°F
11: 20°F
12: 25°F
0: 5°F
1: 10°F
2: 15°F
41